Page 190 - Sace Emax 2 Manual for design engineers
P. 190

Continued from the previous page                                   ABB | SACE Emax 2
                                     Parameter  Description                                                Default
                                                If Self-latching = Off, defines the minimum activation time of the output in the
                                                presence of rapid Sources:
                                                 • Source duration < Min activ. time = the output remains activated for the
                                     min Activation
                                     Time  (2)  duration of the Min activ. time                            0 ms
                                                 • Source duration < Min activ. time = the output remains activated for as long
                                                as the Source persists
                                                Choose between: 0 ms, 100 ms, 200 ms

                                    (1)  deactivate the self-latchings of the outputs used for Power Controller if the module is used for the Power
                                    Controller function
                                    (2)  the Pulse Mode option will be available as well as those described if the module is used for the Power
                                    Controller function. If selected, the output is maintained active for a fixed time pertaining to the function itself,
                                    regardless of whether the event that activated it persists or not.


                   Input parameters All the inputs enable the following parameters to be configured:

                                     Parameter    Description                                             Default
                                                  Defines whether the state of the input is ON when the contacts are open   Active
                                     Polarity
                                                  (Active open) or short-circuited (Active Closed)        closed
                                                  Minimum activation and deactivation time of an input enabling a change of
                                                  state to be recognized by the trip unit; the Delay is given in seconds and can
                                                  be set within a range between 0 s and 100 s, in 0.01 s steps.
                                     Delay            NOTES:                                              0.1 s
                                                      • the trip unit will not detect a change of state if it is present for less
                                                     than the set Delay
                                                      • if Delay = 0 s, the change of state must still be more than 300 mS|ii|




                             About The About-Modules menu contains the specific area for Ekip Signalling 4K, in which the states of the inputs
                                    (On/Off) and outputs (Open/Closed) are present.



                               Test The dedicated area in the Test menu is activated if Ekip Signalling 4K is detected correctly by the trip unit.
                                    For details of the test characteristics, please consult page 134.


            Commands and functions If Self-latching = On, the activated output contacts can be reset with:
                                     •  automatic command RESET signaling, which can be programmed in the Settings-Modules-Functions
                                       menu of Ekip Touch or via Ekip Connect
                                     •  manual command via the service connector (via Ekip Connect) or via system bus communication