Page 212 - Sace Emax 2 Manual for design engineers
P. 212
ABB | SACE Emax 2
Configurations via menu Local bus activation, which is essential for starting the communication between module and Ekip Touch, is
available in the Settings menu (page 46).
The following communication parameters can be configured if the module has been correctly detected by
Ekip Touch in the Settings-Modules menu:
Parameter Description Default
Defines whether the module has the dynamic (Off) or static (On)
Static IP address ON IP address. OFF
Se = On all the associated parameters are enabled
Static address IP address Enables the static IP to be selected 0.0.0.0
Static Network Mask Enables the subnet mask to be selected 0.0.0.0
When there are several subnets, enables the IP address of the
Static Gateway address 0.0.0.0
node to which the module is connected to be selected
Allows the SNTP protocol for distribution of the clock and
Enable SNTP client OFF
synchronization signal to be enabled.
SNTP Server Addr. Allows the network server that supplies the SNTP to be set. 0.0.0.0
Information in menu The following information will be available in the About-Modules menu if Ekip Touch has detected the module
correctly:
Information Description
SN and version Identifier and SW version of the module
Address of the module, assigned to the module by a DHCP server at the time
of connection to the network in the case of configuration with a dynamic IP, or
IP address can be set via the menu in the event of a static IP.
NOTE: without a DHCP server, the module automatically adopts a
random IP address within the 169.254.xxx.xxx range
Subnet mask; identifies the method for recognizing the subnet to which the
Network Mask modules belong and enables modules to be searched for within a defined set
of recipients.
IP address of the node to which the module is connected, in the presence of
Gateway address
several subnets
Address assigned by ABB, with OUI (Organizationally Unique Identifier) equal to
MAC address
ac:d3:64, which uniquely identifies the manufacturer of an Ethernet device
Cfg file Name of the configuration file uploaded to the modules
Cfg file error Code of the error concerning the configuration file (0 = no error)
210 | © 2020 ABB | 1SDH001330R1002 - ECN000134959 - Rev. A External electronic accessories | 8 - Ekip Com IEC 61850