Remote configurations Additional parameters can be accessed via the service connector (via Ekip Connect) or via a system bus
communication:
Parameter Description Default
Preferred If several configuration files are present, allows file hierarchy between .cid
configuration file .cid and .iid to be defined
Allows the IEEE 1588 protocol for distribution of the clock and
Enable IEEE 1558 OFF
synchronization signal to be enabled .
(1)
Enables the module to be set up as a master in the the network
IEEE 1558 Master OFF
segment to which it belongs (synchronization clock).
IEEE 1558 Delay Allows the data exchange mode between module and master, either End-to-
mechanism Peer-to-Peer or End-to-End, to be selected. End
Time zone Defines the time zone to be used for synchronism +00:00
Used to select whether daylight saving time is present (ON) or not
Daylight Saving Time OFF
(OFF) in the country to which the synchronization time refers
Defines the file loading procedure:
• TFTP always On = port open, loading always possible
• TFTP enable required = port normally closed. To start loading, TFTP
TFTP Security level
Enable TFTP must be run at the start of the procedure and Disable always On
TFTP must be run at the end of the procedure (disable not necessary,
security command).
Defines the limitations to remote opening and closing command
execution:
CB Open/CB Close • Standard commands = standard commands (unrestricted) activated Standard
command • CB operate request = standard commands not activated. Use commands
programmable functions YC COMMAND and YO COMMAND, and
Request breaker open (28) and Request breaker close (29) commands
Falg word hex Sets a filter on the selectivity statuses 0
Remote information Additional information can be accessed via the service connector (via Ekip Connect) or via a system bus
communication:
Information Description
HW and Boot version General module information
Flash CRC status and result Information about the correctness of the SW in the module
Ekip Link status Signals Ethernet cable connection errors
SNTP Server Error Error in communication with SNTP server
SNTP Server Synchronization State of synchronism with SNTP server
Valid with Master IEEE 1588= ON, notifies the presence (Slave or PTP
IEEE 1558 status Master Active) or absence (PTP Master but Passive) of a higher level
master
GOOSE Missing Signals that an expected GOOSE has not been received
Configure Mismatch
Decode Error A GOOSE received does not conform to the expected structure
Sequence number error
Remote programmable statuses Condition (true/false) of the programmable states and information on
(from E to R) selectivity arising from logic defined in the configuration files loaded in
Zone selectivity remote inputs module IEC 61850