Page 208 - Sace Emax 2 Manual for design engineers
P. 208
ABB | SACE Emax 2
Connections The module must be assembled in the first vacant slot of the terminal box after Ekip Supply, either on the
circuit-breaker (fixed version) or on the fixed part (withdrawable version).
For references about the connection and terminals, please consult document 1SDM000091r0001; a cable
of the Class 6 S/FTP type (Class 6 with double screening S/FTP) must be used for the communication bus.
To connect the module to Ekip Touch, please consult document 1SDH001000r0514.
Power supply Ekip Com EtherNet/IP is supplied directly by the Ekip Supply module to which it is connected.
TM
NOTE: communication between Ekip Touch and the module is interrupted in the absence of
auxiliary power supply
Interface the module has three signaling leds:
2 1
Figure 131
LEDs Description
Signals the on status and correct communication with Ekip Touch:
• off: module off
• on steady or flashing synchronized with the Power led of Ekip Touch: module on
Power
and communication with Trip unit present.
• flashing not synchronized with the Power led of Ekip Touch (2 fast flashes per
second): module on and communication with Trip unit absent.
Indicates the communication state:
Link (1) • off: incorrect connection, signal absent.
• on steady: connection correct
Indicates the communication state:
Activity (2) • off: no activity on line
• flashing: activity on line present (receiving and/or transmitting)
Configurations via menu Local bus activation, which is essential for starting the communication between module and Ekip Touch, is
available in the Settings menu (page 46).
The following communication parameters can be configured if the module has been correctly detected by
Ekip Touch in the Settings-Modules menu:
Parameter Description Default
Defines whether the module has the dynamic (Off) or static
Static IP address ON (On) IP address. OFF
Se = On all the associated parameters are enabled
Static address IP address Enables the static IP to be selected 0.0.0.0
Static Network Mask Enables the subnet mask to be selected 0.0.0.0
When there are several subnets, enables the IP address of
Static Gateway address 0.0.0.0
the node to which the module is connected to be selected
206 | © 2020 ABB | 1SDH001330R1002 - ECN000134959 - Rev. A External electronic accessories | 7 - Ekip Com EtherNet/IP TM