ABB | SACE Emax 2
Information in menu The following information will be available in the About-Modules menu if Ekip Touch has detected the module
correctly:
Information Description
SN and version Identifier and SW version of the module
Address of the module, assigned to the module by a DHCP server at the time of
connection to the network in the case of configuration with a dynamic IP, or can be
IP address set via the menu in the event of a static IP.
NOTE: without a DHCP server, the module automatically adopts a random IP
address within the 169.254.xxx.xxx range
Subnet mask; identifies the method for recognizing the subnet to which the modules
Network Mask
belong and enables modules to be searched for within a defined set of recipients.
IP address of the node to which the module is connected, in the presence of several
Gateway address
subnets
Address assigned by ABB, with OUI (Organizationally Unique Identifier) equal to
MAC address
ac:d3:64, which uniquely identifies the manufacturer of an Ethernet device
Remote configurations Additional parameters can be accessed via the service connector (via Ekip Connect) or via a system bus
communication:
Parameter Description Default
Enable IEEE Allows the IEEE 1588 protocol for distribution of the clock and OFF
1558 synchronization signal to be enabled .
(1)
IEEE 1558 Enables the module to be set up as a master in the the network OFF
Master segment to which it belongs (synchronization clock).
IEEE 1558 Delay Allows the data exchange mode between module and master, either
mechanism Peer-to-Peer or End-to-End, to be selected. End-to-End
Enable client Allows the SNTP protocol for distribution of the clock and OFF
SNTP synchronization signal to be enabled (1)
ANTP Server Allows the network server that supplies the SNTP to be set. 0.0.0.0
address
Time zone Defines the time zone to be used for synchronism +00:00
Daylight Saving Used to select whether daylight saving time is present (ON) or not
Time (OFF) in the country to which the synchronization time refers OFF
(1) Enable IEEE 1588 and Enable SNTP client must not be enabled at the same time
Remote information Additional information can be accessed via the service connector (via Ekip Connect) or via a system bus
communication:
Information Description
HW and Boot version General module information
Flash CRC status and result Information about the correctness of the SW in the module
Ekip Link status Signals Ethernet cable connection errors
SNTP Server Error Error in communication with SNTP server
SNTP Server Synchronization State of synchronism with SNTP server
Valid with Master IEEE 1588= ON, notifies the presence (Slave or PTP
IEEE 1558 status Master Active) or absence (PTP Master but Passive) of a higher level
master
207 | © 2020 ABB | 1SDH001330R1002 - ECN000134959 - Rev. A External electronic accessories | 7 - Ekip Com EtherNet/IP TM