ABB | SACE Emax 2
Configurations via menu Local bus activation, which is essential for starting the communication between module and Ekip Touch, is
available in the Settings menu (page 46).
The following communication parameters can be configured if the module has been correctly detected by
Ekip Touch in the Settings-Modules menu:
Parameter Description Default
Defines whether the module has the dynamic (Off) or static
Static IP address ON (On) IP address. OFF
Se = On all the associated parameters are enabled
Static address IP address Enables the static IP to be selected 0.0.0.0
Static Network Mask Enables the subnet mask to be selected 0.0.0.0
When there are several subnets, enables the IP address of the
Static Gateway address 0.0.0.0
node to which the module is connected to be selected
Information in menu The following information will be available in the About-Modules menu if Ekip Touch has detected the module
correctly:
Information Description
SN and version Identifier and SW version of the module
Address of the module, assigned to the module by a DHCP server at the time of
connection to the network in the case of configuration with a dynamic IP, or can be
IP address set via the menu in the event of a static IP.
NOTE: without a DHCP server, the module automatically adopts a random IP
address within the 169.254.xxx.xxx range
Subnet mask; identifies the method for recognizing the subnet to which the
Network Mask modules belong and enables modules to be searched for within a defined set of
recipients.
IP address of the node to which the module is connected, in the presence of
Gateway address
several subnets
Address assigned by ABB, with OUI (Organizationally Unique Identifier) equal to
MAC address
ac:d3:64, which uniquely identifies the manufacturer of an Ethernet device
Remote configurations Additional parameters can be accessed via the service connector (via Ekip Connect) or via a system bus
communication:
Parameter Description Default
Parameter for changing the configuration of the module from Server
Only to Client and Server and for integrating it into an interactive
Client/Server data exchange network (see Ekip Com Hub on page216). Server only
IMPORTANT: if Client/Server, the module allows data
exchange like a normal Server function
Allows the IEEE 1588 protocol for distribution of the clock and
Enable IEEE 1558 OFF
synchronization signal to be enabled .
(1)
Enables the module to be set up as a master in the the network
IEEE 1558 Master OFF
segment to which it belongs (synchronization clock).
IEEE 1558 Delay Allows the data exchange mode between module and master, either End-to-End
mechanism Peer-to-Peer or End-to-End, to be selected.
Allows the SNTP protocol for distribution of the clock and
Enable client SNTP Off
synchronization signal to be enabled (1)
ANTP Server address Allows the network server that supplies the SNTP to be set. 0.0.0.0
Time zone Defines the time zone to be used for synchronism +00:00
Used to select whether daylight saving time is present (ON) or not
Daylight Saving Time OFF
(OFF) in the country to which the synchronization time refers
Continued on the next page
214 | © 2020 ABB | 1SDH001330R1002 - ECN000134959 - Rev. A External electronic accessories | 9 - Ekip Link