Page 218 - Sace Emax 2 Manual for design engineers
P. 218
ABB | SACE Emax 2
10 - Ekip Com Hub
Ekip Com Hub is a communication accessory that enables the data and measurements of Ekip Touch and
other devices connected to the same installation to be gathered and then made available on the server
through an Ethernet network.
The configuration of the module is available via Ekip Connect or with the System Interface document, which
contains all the details. (page 182).
The ports used by the module are:
Port Service Notes
67/udp 68/udp DHCP client DHCP client enabled alternatively as Static address = On
443/tcp HTTPS Always active when module is enabled
123/udp SNTP Active with SNTP client enabled
53/udp DNS Always active
The Ekip Com Modbus RTU and Ekip Com Modbus TCP modules can be configured to support Ekip Com
Hub in the collection of data to send to Cloud. See Getting Started 1SDC200063B0201.
Ekip Com Hub is always supplied with contacts Ekip AUP and Ekip RTC (page 234).
Safety and cyber security The module uses the HTTPS protocol and can be connected to the Internet
IMPORTANT:
• it is the customer's sole responsibility to provide and continuously ensure a secure
connection between the module and customer network or any other network (as the
case may be). The plant manager must establish and maintain appropriate measures
(such as but not limited to the installation of firewalls, application of authentication
measures, encryption of data, installation of antivirus programs, etc.) to protect the
product, the network, the customer system and interface against any kind of security
breaches, unauthorized access, interference, intrusion, loss and/or theft of data or
information. ABB and its affiliates are not liable for damages and/or losses related to
such security breaches, unauthorized accesses, interference, intrusion, loss and/or
theft of data or information.
Connections The module must be assembled in the first vacant slot of the terminal box after Ekip Supply, either on the
circuit-breaker (fixed version) or on the fixed part (withdrawable version).
For references about the connection and terminals, please consult document 1SDM000091r0001; a cable
of the Class 6 S/FTP type (Class 6 with double screening S/FTP) must be used for the communication bus.
To connect the module to Ekip Touch, please consult document 1SDH001000r0514.
Power supply Ekip Com Hub is supplied directly by the Ekip Supply module to which it is connected.
NOTE: communication between Ekip Touch and the module is interrupted in the absence of
auxiliary power supply
216 | © 2020 ABB | 1SDH001330R1002 - ECN000134959 - Rev. A External electronic accessories | 10 - Ekip Com Hub