Page 219 - Sace Emax 2 Manual for design engineers
P. 219
ABB | SACE Emax 2
Interface the module has three signaling leds:
2 1
Figure 134
LEDs Description
Signals the on status and correct communication with Ekip Touch:
• off: module off
• on steady or flashing synchronized with the Power led of Ekip Touch: module
Power
on and communication with Trip unit present.
• flashing not synchronized with the Power led of Ekip Touch (2 fast flashes per
second): module on and communication with Trip unit absent.
Indicates the communication state:
Link (1) • off: incorrect connection, signal absent.
• on steady: connection correct
Indicates the communication state:
Activity (2) • off: no activity on line
• flashing: activity on line present (receiving and/or transmitting)
Configurations via menu Local bus activation, which is essential for starting the communication between module and Ekip Touch, is
available in the Settings menu (page 46).
The following communication parameters can be configured if the module has been correctly detected by
Ekip Touch in the Settings-Modules menu:
Parameter Description Default
Enable Switches communication between module and server on/off.
Defines whether the module has the dynamic (Off) or static (On)
Static IP address ON IP address. Off
If = On all the associated parameters are enabled
Static address IP address Enables the static IP to be selected 0.0.0.0
Static Network Mask Enables the subnet mask to be selected 0.0.0.0
When there are several subnets, enables the IP address of the
Static Gateway address 0.0.0.0
node to which the module is connected to be selected
Allows the SNTP protocol for distribution of the clock and
Enable SNTP client Off
synchronization signal to be enabled.
SNTP Server Addr. Allows the network server that supplies the SNTP to be set. 0.0.0.0
Password code required to register module on Cloud ---
Enables the firmware of the module to be updated. There are two
parameters: Off
Remote firmware update
• Enable, to configure firmware download Automatic
• Automatic, to automate module updating
217 | © 2020 ABB | 1SDH001330R1002 - ECN000134959 - Rev. A External electronic accessories | 10 - Ekip Com Hub