Page 264 - Sace Emax 2 Manual for design engineers
P. 264

ABB | SACE Emax 2
       2 - Self-diagnosis



                  Alarms and signals  Alarm Tests
                                    Ekip Touch provides a series of signals that indicate its operating state, alarms present, or configuration errors
                                    in progress.
                                    The signals are provided:
                                     •  By LEDs, as described on page 36.
                                     •  By messages on the diagnosis bar.
                                    The messages on the diagnostics bar can be divided into three categories: self-diagnosis, protection or
                                    measurement alarms, and programming error.



                Alarms displayed and  A list of faults that may appear on the Ekip Touch display is given below along with suggestions on how to
                        suggestions resolve them:
                                     Signal             Suggestions
                                     Numerical alarm (e.g.   Internal error; contact ABB if this typoe of error occurs
                                     30002)
                                     Battery low        Change the battery (See 1SDH001000R0509 kit sheet)
                                                        Unit on with auxiliary supply, Local Bus parameter enabled but connection
                                                        to modules not present, incorrect or communication lost (for more than five
                                     Local bus          seconds); check:
                                                         • connection and powering of modules in terminal box or external
                                                         • that the moldules connected are compatible with Ekip Touch
                                     CB undefined       Check the circuit-breaker status signal contacts
                                                        CB has failed to open and/or current still present after a TRIP command:
                                     Trip fail command (BF)  comply with the procedure proposed in the next chapter 'Faults, causes and
                                                        remedies'
                                                        Protection parameter configuration error: make sure that threshold I4 and time
                                                        t4 are compatible with the minimum values required for self-supply
                                                        Check:
                                                         • Rating plug of model compatible with Ekip Touch and CB size
                                     Configuration       • If present, protection parameters do not conflict with size of current of unit
                                                        details on page 20 51)
                                                         • In the absence of Vaux threshold I4 and/or I41 > 100 A
                                                         • In the absence of Vaux time t4 and/or t41 > 100 ms
                                                         • RC protection active and Rating Plug not RC
                                     Invalid Date       Wrong date and time: set in Settings-System-Date and Settings-System-Time
                                                        Problem of Ekip Com Hub module with: certificates, connected devices,
                                     Ekip Com Hub       missing Com modules (RTU or with Ethernet connection), API TLS device, Hub
                                                        events, parsar configuration
                                                        Fault in Ekip Link module: check for loss of connection with one or more actors
                                     Ekip Link Bus
                                                        (modules) connected to Link Bus
                                     Ekip Sign 3T connection  Alarm for connection of one or more analog inputs to Ekip Signalling 3T module
                                                        One or more thresholds of the Ekip Signalling 3T module has/have been
                                     Ekip Sign 3T threshold
                                                        exceeded
                                     Internal error     Internal error; contact ABB if this typoe of error occurs
                                                        Fault with Ekip Com modules: synchronization problem of SNTP
                                     SNTP error
                                                        synchronization reference module
                                     Measuring Error    Measurement module parameter reading error, contact ABB
                                     Ethernet disconnected  No external cable on one or more Ekip Com modules with Ethernet connection
                                     IEEE1588 synch     Synchronization problem of IEEE 1588 synchronization reference module
                                                        Ekip Com module detected with incorrect / not allowed MAC address, contact
                                     MAC Address
                                                        ABB.


                                                                                                  Continued on the next page







       262 | © 2020 ABB |  1SDH001330R1002 - ECN000134959 - Rev. A                            Alarms or failures | 2 - Self-diagnosis