Page 265 - Sace Emax 2 Manual for design engineers
P. 265

Continued from the previous page                                   ABB | SACE Emax 2
                                     Signal             Suggestions
                                     Ekip Installation  Installation error between HMI and Mainboard, contact ABB
                                                        Install Measurement module (Settings-Circuit breaker-Installation-Measuring-
                                     Measuring installation
                                                        Install) menu
                                                        Install Rating Plug (Settings-Circuit breaker-Rating Plug-Install menu) and check
                                     RatingPlugInstallation
                                                        connection if there are further faults
                                                        Maintenance alarm: perform maintenance and then reset the alarm via Ekip
                                     Maintenance
                                                        Connect (see 1SDH001330R1002)
                                     PC Power exceed    The average power limit setting of the Power Controller has been exceeded
                                     Rating plug        Rating plug not present, value or size incompatible with Ekip Touch parameters
                                     Zone Selectivity Diag  Error in zone selectivity connections (Hardware Selectivity)
                                     Toroid S.G.R.      Check connection and state of current sensor
                                                        Fault in connection of sensors to Trip unit; check status of sensors, including
                                     Sensor L1/L2/L3/Ne  external Neutral, or call ABB
                                                        Check current sensors, status of terminal and cables connecting to Ekip Touch
                                                        TFTP server enabled and/or configuration session open on module Ekip Com
                                     Configuration Session
                                                        IEC61850 or Ekip Hub
                                                        The software versions between Mainboard and display (Ekip Touch) are not
                                                        compatible with each other: To restore compatibility, please consult ABB.
                                                            NOTE: modification of all parameters is inhibited via display; if present,
                                     Software Not Compatible
                                                            protections L, I and Iinst are active and function with the parameters prior
                                                            to the alarm (parameters of previous unit are active if display has been
                                                            replaced)
                                     CB status          CB state incorrect (esample: current present but CB in open state)
                                     Switchboard Actor   Check configuration and connection of Ekip Link module
                                     communication Error
                                                        Disconnection of Trip coil detected, check functionality
                                     TC disconnected
                                                        Check Trip coil, status of the terminal and cables connecting to Ekip Touch
                                     Contact Wear       Make sure that the contacts/poles are in good condition.


                                    Protections
                                    In the event of protection or measurement alarms, the associated signals are reported:
                                     Signal                                 Type of alarm
                                                                            Trip test performed signal. Press iTEST to reset the
                                     Trip Test
                                                                            message
                                     Protection timing (for example: L timing)  Specific protection in time delay mode
                                     Protection prealarm (for example: Prealarm G)  Specific protection in prealarm
                                                                            Specific protection, configured with trip disabled, in
                                     Protection (Trip off) [for example: S (Trip off) ]
                                                                            alarm state
                                     2I Protection Active                   2I Protection active
                                                                            Current threshold 1 I1 / 2 I1 exceeded and in alarm
                                     Load LC1 / Load LC2
                                                                            state
                                                                            Current threshold Iw1 / Iw2 exceeded and in alarm
                                     Iw1 Warning / Iw2 Warning
                                                                            state
                                     Harmonic dist.                         Harmonic Distortion protection in alarm state
                                                                            Power factor measurement (cos φ) less than set
                                     Power factor
                                                                            threshold
                                     Phase cycle                            Phase sequence protection in alarm state
                                     Frequency                              Frequency measured off range (<30 Hz or >80 Hz)
                                     5th harmonic above Th / I sopra Th / THD I above   Single or total harmonic measurement above
                                     Th / THD V above Th                    threshold












       263 | © 2020 ABB |  1SDH001330R1002 - ECN000134959 - Rev. A                            Alarms or failures | 2 - Self-diagnosis