Continued from the previous page ABB | SACE Emax 2
Signal Suggestions
Ekip Installation Installation error between HMI and Mainboard, contact ABB
Install Measurement module (Settings-Circuit breaker-Installation-Measuring-
Measuring installation
Install) menu
Install Rating Plug (Settings-Circuit breaker-Rating Plug-Install menu) and check
RatingPlugInstallation
connection if there are further faults
Maintenance alarm: perform maintenance and then reset the alarm via Ekip
Maintenance
Connect (see 1SDH001330R1002)
PC Power exceed The average power limit setting of the Power Controller has been exceeded
Rating plug Rating plug not present, value or size incompatible with Ekip Touch parameters
Zone Selectivity Diag Error in zone selectivity connections (Hardware Selectivity)
Toroid S.G.R. Check connection and state of current sensor
Fault in connection of sensors to Trip unit; check status of sensors, including
Sensor L1/L2/L3/Ne external Neutral, or call ABB
Check current sensors, status of terminal and cables connecting to Ekip Touch
TFTP server enabled and/or configuration session open on module Ekip Com
Configuration Session
IEC61850 or Ekip Hub
The software versions between Mainboard and display (Ekip Touch) are not
compatible with each other: To restore compatibility, please consult ABB.
NOTE: modification of all parameters is inhibited via display; if present,
Software Not Compatible
protections L, I and Iinst are active and function with the parameters prior
to the alarm (parameters of previous unit are active if display has been
replaced)
CB status CB state incorrect (esample: current present but CB in open state)
Switchboard Actor Check configuration and connection of Ekip Link module
communication Error
Disconnection of Trip coil detected, check functionality
TC disconnected
Check Trip coil, status of the terminal and cables connecting to Ekip Touch
Contact Wear Make sure that the contacts/poles are in good condition.
Protections
In the event of protection or measurement alarms, the associated signals are reported:
Signal Type of alarm
Trip test performed signal. Press iTEST to reset the
Trip Test
message
Protection timing (for example: L timing) Specific protection in time delay mode
Protection prealarm (for example: Prealarm G) Specific protection in prealarm
Specific protection, configured with trip disabled, in
Protection (Trip off) [for example: S (Trip off) ]
alarm state
2I Protection Active 2I Protection active
Current threshold 1 I1 / 2 I1 exceeded and in alarm
Load LC1 / Load LC2
state
Current threshold Iw1 / Iw2 exceeded and in alarm
Iw1 Warning / Iw2 Warning
state
Harmonic dist. Harmonic Distortion protection in alarm state
Power factor measurement (cos φ) less than set
Power factor
threshold
Phase cycle Phase sequence protection in alarm state
Frequency Frequency measured off range (<30 Hz or >80 Hz)
5th harmonic above Th / I sopra Th / THD I above Single or total harmonic measurement above
Th / THD V above Th threshold
263 | © 2020 ABB | 1SDH001330R1002 - ECN000134959 - Rev. A Alarms or failures | 2 - Self-diagnosis