Page 263 - Sace Emax 2 Manual for design engineers
P. 263

ABB | SACE Emax 2
                 Programming errors If during the programming of the parameters an attempt is made to violate certain limitations, the trip unit
                                    blocks the saving procedure and signals the error:
                                     Type of error             Error description
                                     2I Th > 15kA              Threshold I31 (protection 2I) > 15kA
                                     30006                     Parameter change not completed on display within five minutes
                                     30007                     Attempt at remote control with Trip unit configuration in the local mode
                                     30008                     Attempt at local control with Trip unit configuration in the remote mode
                                     30011                     Error in Ekip Link list of actors
                                                               More than one Time Sync source (IEEE1588 or SNTP) on one single
                                     30012
                                                               module or between different modules
                                     30013                     Network Analyzer parameter control unsuccessful
                                     Active Power Fail         Threshold P23 (protection UP) ≥ Threshold P26 (protection OP)
                                                               Modification of datalogger parameters not allowed with datalogger
                                     DLog not stopped
                                                               function not stopped
                                     D Th ≥ I Th               Threshold I7 (protection D) ≥ Threshold I3 (protection I)
                                                               Zone selectivity enabling of protection D not allowed with zone
                                     D Zone Sel = On while S / S2 / I /   selectivity already active for one among protections S, S2, I, G, Gext
                                     G / Gext / MDGF = On
                                                               or MDGF
                                                               Threshold I4 (protection G) or Threshold I41 (protection Gext or
                                     G Th > 1200A
                                                               MDGF) > 1200A with CB in standard configuration UL
                                                               G or Gext or MDGF > 1200A protection threshold start up with CB in
                                     G Startup Th > 1200A
                                                               standard configuration UL
                                     G FT time = 50 ms is not valid  Trip time I4 (protection G) = 50 ms
                                                               Trip time t4 (protetion G) > 400ms with CB in standard configuration
                                     G Time> 400 ms
                                                               UL
                                                               Trip time t41 (protetion Gext or MDGF) > 400ms with CB in standard
                                     Gext Time> 400 ms
                                                               configuration UL
                                     Gext FT time = 50ms isn't valid  Trip time I41 (protection G) = 50 ms
                                     High priority alarm       Modification of parameters not allowed during protection times
                                     I and MCR enabled together  Protections I and MCR are mutually exclusive
                                     L Th ≥ S Th               Threshold I1 (protection L) ≥ Threshold I2 (protection S)
                                     L Th ≥ S2 Th              Threshold I1 (protection L) ≥ Threshold I5 (protection S2)
                                                                                           2
                                                               Protection curve L different from t=k/I  with CB in standard
                                     L curve different to I t=k
                                                    2
                                                               configuration UL
                                     L Th >980A                Threshold I1 (protetion I)> 980A with CB in standard configuration UL
                                                               Configuration of neutral protection must conform to formula: I1 (A) ≥ Iu
                                     Neutral configuration error
                                                               (A) x Ne config / 100
                                     OV Threshold > 828 V      Threshold U9 (Protection OV) > 828V (690 x1.2)
                                     OV2 Threshold > 828 V     Threshold U16 (Protection OV2) > 828V (690 x1.2)
                                                               Activation of toroid Rc is not allowed without the presence of a model
                                     RC toroid error
                                                               Rc rating plug
                                     RQ Q24  ≥ Q27             Threshold Q24 ≥ Threshold Q25 (Protection RQ)
                                     S Th ≥  I Th              Threshold I2 (Protection S) ≥ Threshold I3 (Protection I)
                                     S2 Th ≥ I Th              Threshold I5 (Protection S2) ≥ Threshold I3 (Protection I)
                                                               Trip time t2 (protetion S) > 400ms with CB in standard configuration
                                     S Time > 400 ms
                                                               UL
                                                               Trip time t5 (protetion S2) > 400ms with CB in standard configuration
                                     S2 Time> 400 ms
                                                               UL
                                                               Error in configuration of parameters of protection S (V) or S2 (V);
                                     S(V) or S2(V) parameters
                                                               consult user manual of Trip unit for the limits
                                                               Inconsistency of Synchrocheck protection parameters: Delta phase ≥
                                     SYNCHRO parameters error
                                                               180 x Delta freq x [minimum correspondence time + 0.0023]
                                     V DIR Th > 690*1.4        Protection threshold VDIR > 828V (690 x1.2)
                                     VS Th > 690*1.4           One of the two thresholds of protection VS Warning > 828V (690 x1.2)







       261 | © 2020 ABB |  1SDH001330R1002 - ECN000134959 - Rev. A                  Alarms or failures | 1 - Identification of alarms or failures