ABB | SACE Emax 2
                       2I Protection Function
                                    If the current of one or more phases exceeds threshold I31 and a trip event is present, the protection
                  t                 transmits the TRIP command after a non-programmable fixed time.
                       I31    2I
                                    To check and simulate the trip times in relation to all the parameters, please consult:
                                     •  summary table of the protections with the operating characteristics (page 92)
                                     •  the graph with trip curve (page 99)
                                     Parameter    Description                                         Default
                                  I               Activates/deactivates the protection and its availability in the
                                     Enable                                                           OFF
                                                  parameters menu.
                                                  Establishes the value that activates the protection.
                                     Threshold I31  The value is given as both absolute value (A) and relative value (In) and  1,5 In
                                                  can be set within the range: 1.5 In to 15 In, in 0.1 In steps

                                    Protection enabling makes the  2I Mode section available in the  Advanced - Functions menu, where the
                                    protection activation event can be configured:
                                     Parameter    Description                                         Default
                                                  Two alternative modes are available:
                                                   • Dependent function: the protection is activated if the programmed
                                     Activation   activation event has occurred; this configuration makes the function   Dependent
                                                                                                      function
                                                  and delay parameters available
                                                   • Activated: the protection is always activated
                                                  The activation event between the input contacts of Ekip Signalling 2K,
                                                  the statuses of the unit (open/closed) and the Custom function can be
                                                  selected
                                     Function                                                         Disabled
                                                      NOTE: Ekip Connect allows the Custom function to be
                                                     customized so as to associate the activation event with up to
                                                     eight statuses in AND or OR configuration
                                                  Protection activation delay calculated from the presence of the
                                                  activation event onwards.
                                                  The value is given in seconds and can be set within the range: 0 s to
                                     Delay                                                            0 s
                                                  100 s, in 0.1 s steps
                                                      NOTE: the protection trips if the event is present for longer than
                                                     the set time lag


                                    RELT - Ekip signalling 2K-3
                                    If the RELT module is present a dedicated command (RELT Wizard) will be displayed. This will program the 2I
                                    protection and other related parameters; for details see page 220.
                                    Commands by remote control
                                    Two further temporary protection activation/deactivation commands are available when the unit is connected
                                    to one or more Ekip Com modules:
                                     •  2I ON Mode: activates the protection
                                     •  2I OFF Mode: deactivates the protection
                                    For further details consult the document 1SDH001140r0001.
                                           NOTE: if the protection has been activated by command 2I ON Mode, it is deactivated by
                                               command 2I OFF Mode or when the unit shuts down

                                    Signallings
                                    When protection 2I is activated, the message “2I active” appears in the diagnostic bar and in the Alarm List
                                    page, and the alarm led will be on steady.