                       G Protection Function
                                    Ekip Touch calculates the vector sum of the phase currents (L1, L2, L3, Ne) and obtains the internal earth
                  t                 fault current (Ig): if current Ig exceeds threshold I4, the protection trips and, after a time established by the
                       I4     G     value read and by the parameter settings, transmits the TRIP command.
                                    To check and simulate the trip times in relation to all the parameters, please consult:
                                     •  the summary table of the protections with the calculation formulas (page 92)
                            t4
                                     •  the graph with trip curve (page 100)
                                    Parameters
                                  I
                                     Parameter    Description                                           Default
                                                  Activates/deactivates the protection and its availability in the parameters
                                     Enable                                                             OFF
                                                  menu.
                                                  Activates/deactivates transmission of the open command. if disabled,
                                     Trip Enable  the alarm and exceedance of protection time are only managed as   ON
                                                  information.
                                                  Establishes curve dynamics and the threshold or trip time calculation:
                                     Curve             • t = k: fixed time trip                         t = k
                                                             2
                                                       • t = k/I : inverse time-delay dynamic trip
                                                  Establishes the value that activates the protection and contributes
                                                  towards calculating the trip time.
                                     Threshold I4                                                       0,2 In
                                                  The value is given as both absolute value (A) and relative value (In) and
                                                  can be set within the range: 0.1 In to 1 In, in 0.001 In steps
                                                  It is the trip time or contributes towards timing calculation, depending on
                                                  the type of curve selected.
                                                  The value is given in seconds and can be set within the range: 0.1 s to 1
                                     Time t4      s, in 0.05 s steps                                    0,4 s
                                                      NOTE: in the presence of curve: t = k, t4 can also be configured as:
                                                     instantaneous; in this mode, the trip time is comparable to that
                                                     given for I protection (page 92)
                                                  Warns that the measured current is near to the protection activation
                                                  threshold.
                                                  The value is given in percentage of threshold I1 and can be set within the
                                     Prealarm I4  range 50% I4 to 90% I4, in 1% steps.                  90 % I4
                                                  The prealarm condition deactivates in two cases:
                                                       • current lower than prealarm threshold I4
                                                       • current higher than threshold I4
                                                  Activates/deactivates the function and selectivity time availability on the
                                                  display (page 80)
                                     ZoneSelectivity                                                    OFF
                                                      NOTE: the function is only available with curve t = k

                                                  This is the trip time of the protection with the zone selectivity function
                                                  activated and selectivity input not present (page 80)
                                     Selectivity time                                                   0,04 s
                                                  The value is given in seconds and can be set within the range: 0.04 s to
                                                  0.2 s, in 0.01 s steps
                                                  Activates/deactivates the function and availability of the associated
                                     StartUp enable                                                     OFF
                                                  parameters on the display (page 83)
                                                  Protection threshold valid during Startup time, in the conditions in which
                                     StartUp      the function is activated (page 83)
                                     Threshold    The value is given as both absolute value (A) and relative value (In) and   0,2 In
                                                  can be set within the range: 0.2 In to 1 In, in 0.1 In steps
                                                  This is the time for which the StartUp threshold remains activated, as
                                                  calculated from the moment the activation Threshold is exceeded (page
                                     StartUp Time  83)                                                  0.1 s
                                                  The value is given in seconds and can be set within the range: 0.1 s to 30
                                                  s, in 0.01 s steps