ABB | SACE Emax 2
       3 - Voltage protections



                               List The Voltage protections, available by default for Ekip Hi-Touch, Ekip G Touch, Ekip G-Hi Touch models and
                                    configurable in the remaining models as additional SW package, are:
                                     Name               Type of protection                     Page
                                     UV                 Minimum voltage                        62
                                     OV                 Maximum voltage                        63
                                     UV2  (1)           Minimum voltage                        63
                                     OV2  (1)           Maximum voltage                        64
                                     Phase Sequence     Phase sequence error                   64
                                     VU                 Voltage unbalance                      64

                                    (1)  protections UV2 and OV2 are not available by default with Ekip G Touch. However, they can be integrated by
                                    requesting the relative SW package


                      UV Protection Function
                                    The protection sends a TRIP command if one or more line-to-line voltages detected by the unit drop below
                  t                 threshold U8 for longer than t8.
                              UV
                         U8         To check and simulate the trip times in relation to all the parameters, please consult:
                                     •  summary table of the protections with the operating characteristics (page 93)
                     t8              •  the graph with trip curve (page 102)
                                    Parameters
                                 v   Parameter  Description                                             Default
                                                Activates/deactivates the protection and its availability in the parameters
                                     Enable                                                             OFF
                                                menu
                                                Activates/deactivates transmission of the open command: if disabled, the
                                     Trip Enable                                                        OFF
                                                alarm and exceedance of protection time are only managed as information
                                                Establishes the value that activates the protection.
                                     Threshold U8 The value is given as both absolute value (Volts) and relative value (Un) and  0,9 Un
                                                can be set within the range: 0.05 Un to 1 Un in 0.001 Un steps
                                                This is the trip time of the protection; the value is given in seconds and can
                                     Time t8                                                            5 s
                                                be set within a range: 0.05 s to 120 s, in 0.01 s steps

                                    Limitations and additional functions
                                    The block functions can also be accessed by means of the service connector (via Ekip Connect) or by
                                    connection to the system bus (page 83).



































       62 | © 2020 ABB |  1SDH001330R1002 - ECN000134959 - Rev. A                      Ekip Touch - Protections | 3 - Voltage protections