Page 163 - SACE Tmax XT - Catalogue
P. 163

ACCESSORIES                                                                       7/17





















                           Auxiliary contacts - AUX
                           The SACE Tmax XT circuit-breakers can be equipped with auxiliary contacts that signal the status of the
                           breaker and can be routed outside the circuit-breaker itself. The following information is available:
                           •  open/closed (Q): indication of the status of the circuit-breaker power contacts;
                           •  trip (SY): signals that the circuit-breaker is opening due to the intervention of the trip unit, or to the
                            intervention residual current device, or to the opening of undervoltage releases, or to the use of the
                            emergency opening pushbutton of the motor operator, or to the use of the test button;
                           •  trip unit tripping (S51): indicates that one of the protection functions of the electronic or ther-
                            mal-magnetic trip unit has tripped. In case of the Tmax XT5 equipped with thermal-magnetic trip unit
                            and residual current device, S51 is activated also by the intervention of the residual current device.
                           •  YO/YU tripping (S52): indicates that the under voltage or shunt opening release has been activated.
                            The signaling depends on the service release used. For Tmax XT6 S52 can be used only with YU and is
                            not available for YO. For Tmax XT5, in case of YO, shunt opening release must be permanently sup-
                            plied to maintain the S52 signal.

                           AUX for XT1, XT2, XT3, XT4, XT5 and XT6
                           Circuit -breakers XT1-XT3  XT2-XT4       XT5                   XT6
                           AUX          Q     SY   Q     SY   S51   Q    SY    S51  S52   Q    SY    S51  S52
                           24V DC                                                             
                           250V AC/DC                                                         
                           400V AC      -     -             -              -    -     -    -     -    -


                           24V DC and 250V AC/DC auxiliary contacts
                                                                                                                       07
                           Auxiliary contacts Q (open/closed), SY (trip), S51 (trip unit tripping) and S52 (YO/YU tripping) status during sequences
           Q    SY   S51
          12  14  96  98  06  08  Actions                                Q         SY       S51       S52
                           Normal Sequence           CB Opened           12        96       06        26
                                                     CB Closed           14        96       06        26
                           Trip sequence (caused by: Trip Test) CB Opened  12      96       06        26
             11   95   05
                                                     CB Closed           14        96       06        26
                                                     CB Tripped          12        98       06        26
                                                     CB Reset            12        96       06        26
           S52
          26  28           Trip sequence (caused by: trip unit)  CB Opened  12     96       06        26
                                                     CB Closed           14        96       06        26
                                                     CB Tripped          12        98       08        26
                                                     CB Reset            12        96       06        26
             25            Trip sequence (caused by: YU / YO)  CB Opened  12       96       06        26
                                                     CB Closed           14        96       06        26
                                                     CB Tripped          12        98       06        28
                                                     CB Reset            12        96       06        26
   158   159   160   161   162   163   164   165   166   167   168