Page 166 - SACE Tmax XT - Catalogue
P. 166

7/20             SACE TMAX XT LOW VOLTAGE MOLDED CASE CIRCUIT-BREAKERS



          —

          Signaling













                           AUX 250V AC/DC - Electrical specifications
                           Power supply voltage  Operating current according to the utilization category
                                               AC-15      AC-14     AC-13      DC-14      DC-13      DC-12
                           250V AC             4 A        5 A       6 A        -          -          -
                           125V AC             5 A        6 A       6 A        -          -          -
                           250V DC             -          -         -          0.03 A     0.03 A     0.3 A
                           110V DC             -          -         -          0.05 A     0.05 A     0.5 A

                           AUX 24V DC - Electrical specifications
                           Power supply voltage                       Operating current
                           5 V DC                                     0.001 A
                           30 V DC                                    0.1 A

                           400V AC auxiliary contacts
                           400V AC auxiliary contacts are available only for the XT2, XT4 and XT5 circuit-breakers in the following versions:
                                                         2
                           •  cabled (AWG17 cable section -1mm ):
                               - for fixed/plug-in circuit-breakers with 1m long cables;
                               - for withdrawable circuit-breakers with a fixed part and moving part connector.
                           With the XT2 and XT4, the 400V auxiliary contacts take up the whole right-hand slot of the circuit-
                           breaker. For the XT5 1Q+1SY, the 400V auxiliary contacts are available only with thermal-magnetic or
                           Ekip Dip trip units.
          —
          Cabled auxiliary contact  Combinations  XT2              XT4                   XT5
                                            3/4p                   3/4p                  3/4p
                           1Q 1SY 400V      F-P-W                  F-P-W                 F-P-W  (1)
                           2Q 400V          F-P-W                  F-P-W                 F-P-W
                           F = Fixed, P = Plug-in, W = Withdrawable
                           (1) Only for circuit-breakers with thermal-magnetic or Ekip Dip trip units.
   161   162   163   164   165   166   167   168   169   170   171