Page 168 - SACE Tmax XT - Catalogue
P. 168

7/22             SACE TMAX XT LOW VOLTAGE MOLDED CASE CIRCUIT-BREAKERS



          —

          Signaling













                           AUX for XT7 and XT7 M

                           Circuit -breakers XT7                                 XT7 M
                           AUX          Q         SY         S51       S52       Q         S51       RTC
                           24V DC                                                              
                           250V AC/DC    (1)      (1)                         (1)              
                           400V AC                         -         -                  -         -
                           (1) Same commercial code of AUX 400V


                           Open / closed auxiliary contacts - Q
                           The XT7 and XT7 M circuit-breakers can be equipped with auxiliary contacts that signal the open or
                           closed status of the circuit-breaker. The contacts are available in the following configurations:

                           Open / closed auxiliary                   XT7                  XT7 M
          —                contacts (AUX 4Q)
          Open and close   4 auxiliary contacts  4Q 400V AC/DC                           
          auxiliary contacts
                                                4Q 24V DC                                
                                                2Q 400V AC/DC + 2Q 24V DC                
                           15 auxiliary contacts  15Q 400V AC/DC                          
                                                15Q 24V DC                                

                                                                     400V/250V AC/DC contact  24V DC contact
                           Type                                      Changeover contacts  Changeover contacts
                           Minimum load                              100mA @ 24V          1mA @ 5V
                           Breaking capacity
          —                DC                   24V                  -                    0.1A
          15 auxiliary contacts
                                                125V                 0.3A @ 10ms          -
                                                250V                 0.15A @ 10ms         -
                           AC                   250V                 5A @ cosϕ 1          -
                                                                     5A @ cosϕ 0.7        -
                                                                     5A @ cosϕ 0.3        -
                                                400V                 3A @ cosϕ 1          -
                                                                     2A @ cosϕ 0.7        -
                                                                     1A @ cosϕ 0.3        -
                           The AUX 15Q is an alternative to the mechanical interlock (MI) or the DLC for XT7 M lock.