7/32             SACE TMAX XT LOW VOLTAGE MOLDED CASE CIRCUIT-BREAKERS



          —

          Remote control













                           Installation in circuit-breakers:
                           •  3-pole: as an alternative, the SOR or UVR can be installed in the slot on the left of the operating lever;
                           •  4-pole: the SOR or UVR can be housed at the same time in the slot of the third and fourth pole. For
                            withdrawable circuit-breakers, the connector for the fourth pole must be ordered to be able to install
                            the SOR and UVR in the fourth pole. If there is a residual current release, the opening solenoid (RC SA) of
                            the residual current device must be installed in the slot of the third pole on the left of the operating
                            lever.







                                                                                                  SOR
                              SOR                            SOR                                  UVR
                              UVR                            UVR                                 RC SA









                           SOR Electrical specifications
                           Version                   Max power absorbed on inrush  Resistance
                                                     AC [VA]        DC [W]         Internal [ohm]  External [ohm]
                           12V DC                                   50             2.67          0
                           24-30V AC/DC              50             50             11            0
                           48-60V AC/DC              60             60             62            0
                           110...127V AC-110...125V DC  50          50             248           0
                           220...240V AC-220...250V DC  50          50             930           0
                           380-440V AC               55                            2300          0
                           480-525V AC               55                            5830          0
                           Opening time
                           XT1, XT2, XT3 and XT4     30ms

                           UVR Electrical specification
                           Version                   Power absorbed during normal operation Resistance
                                                     AC [VA]        DC [W]         Internal [ohm]  External [ohm]
                           24-30V AC/DC              1.5            1.5            399           0
                           48V AC/DC                 1              1              1447          100
                           60V AC/DC                 1              1              2405          100
                           110...127V AC-110...125V DC  2           2              8351          390
                           220...240V AC-220...250V DC  2.5         2.5            20502         9000
                           380-440V AC               3                             20502         39000
                           480-525V AC               4                             20502         59000
                           Opening time
                           XT1, XT2, XT3 and XT4     30ms
   173   174   175   176   177   178   179   180   181   182   183