Page 177 - SACE Tmax XT - Catalogue
P. 177

ACCESSORIES                                                                       7/31



          —

          Remote control














                           Remote control                              XT1  XT2  XT3  XT4  XT5  XT6  XT7  XT7 M
                                        SOR - Shunt opening release                    -    -    -    -
                                        UVR - Undervoltage release                     -    -    -    -
                           Service release  YO - Shunt opening release  -   -    -    -                
                                        YU - Undervoltage release      -    -    -    -                
                                        YC - Shunt closing release     -    -    -    -    -    -    -    
                           Remote reset  YR - Resetting remotely       -    -    -    -    -    -    -    
                           YO/YC Test Unit  YO/YC Test Unit                                        
                           Time delay
                           device for YU  UVD - Time delay device for YU                           
                                        MOD                                -        -    -    -    -    -
                                        MOE                            -        -                -    -
                           Motor operator
                                        MOE-E                          -        -            -    -    -
                                        M - Motor                      -    -    -    -    -    -    -    


                           Service releases
                           The SACE Tmax XT circuit-breakers can be fitted with service releases (shunt opening release, shunt
                           closing release for XT7M only and undervoltage release).

                           XT1, XT2, XT3 and XT4

                           Shunt opening release – SOR
                           This allows the circuit-breaker to open by means of a non-permanent electrical control. Release opera-  07
                           tion is guaranteed for voltage between 70% and 110% of the rated power supply voltage Un, in both al-
                           ternating and direct current. The SOR is equipped with a built-in limit contact to shut-off the power
                           supply in the open position with the trip unit tripped.
          —
          Cabled SOR - UVR

                           Undervoltage release – UVR
                           This allows the circuit-breaker to open when the release is subject either to a power failure or a voltage
                           drop. As prescribed in the standards, opening is guaranteed when the voltage is between 70% to 35%
                           Un. After tripping, the circuit-breaker can be closed again if the voltage exceeds the 85% Un. When the
                           undervoltage release is not energized, neither the circuit-breaker or the main contacts can be closed. A
          —
          Cabled SOR - UVR for   remote-controlled emergency opening command can be generated by connecting an opening button to
          withdrawable circuit-  the UVR.
          breaker
                           None of the service releases require screws for installation. They are extremely easy to fit. Just use slight
                           pressure in the appropriate place. All service releases are available in two versions:
                           •  cabled (AWG20 cable section - 0.5mm  up to 300V, AWG17 - 1mm  up to 525V):
                                                           2
                                                                                2
                             -  for fixed/plug-in circuit-breakers with 1m long cables;
         —                   -  for withdrawable circuit-breakers with a fixed and moving part connector;
         Uncabled SOR - UVR
                           •  not cabled:
                                                                            2
                             -  for fixed/plug-in circuit-breakers with cables from 1.5 mm  in cross-section.