Page 173 - SACE Tmax XT - Catalogue
P. 173
ACCESSORIES 7/27
Early Auxiliary Contacts – AUE for XT7
400V/250V AC/DC contact
Type Switching
Minimum load 100mA @ 24V
Breaking capacity
DC 125V 0.3A
250V 0.15A
AC 250V 12A
400V (1) 3A
(1) Only ENEC approved
Ready to close signaling contact - RTC
The ready to close signaling contact – RTC – indicates that the circuit-breaker is ready to receive the
closing command and is available only for the XT7 M. The circuit-breaker is ready to close when the fol-
lowing conditions are fulfilled:
• the circuit-breaker is open
• the springs are loaded
• there are no opening command or locks on the opening command
• the circuit-breaker is reset following tripping of the Ekip protection trip unit.
250V AC/DC contact 24V DC contact
— Type Switching Switching
Ready to close Minimum load 100mA @ 24V 1mA @ 5V
signaling contact
Breaking capacity
DC 24V - 0.1A
250V 0.5A @ 0ms / 0.2A @ 10ms - 07
AC 250V 3A @ cosϕ 0.7 -
Contact signaling loaded springs - S33 M/2
This contact is available for XT7 M only and signals the spring status of the circuit-breaker operating
mechanism. It is available in both 400V AC/DC and 24V DC versions.
400V AC/DC contact 24V DC contact
Type Changeover contacts Changeover contacts
Minimum load 100mA @ 24V 1mA @ 5V
Breaking capacity
DC 24V - 0.1A
125V 0.3A @ 10ms -
250V 0.15A @ 10ms -
AC 250V 5A @ cosϕ 1 -
5A @ cosϕ 0.7 -
5A @ cosϕ 0.3 -
400V 3A @ cosϕ 1 -
2A @ cosϕ 0.7 -
1A @ cosϕ 0.3 -
Mechanical signaling of tripping the protection trip unit - TU Reset
XT7 M circuit-breakers are always equipped with a mechanical device that signals the tripping status of
the protection trip units. After the Ekip trip unit has been tripped due to an electrical fault, the signaling
device clearly indicates the tripping status on the front of the circuit-breaker. The circuit-breaker can be
—
TU Reset reset only after the signaling pushbutton has been restored to its normal operating position.