THE RANGES                                                                        2/11










                                                                                                                       02










 Size  XT1                                  XT2                                                XT3
 Rated uninterrupted current  [A]  160      160                                                250
 Poles  [No.]  3, 4                         3, 4                                               3, 4
 Rated service voltage, Ue  (DC)  [V]  500  500                                                500
 Rated insulation voltage, Ui  (DC)  [V]  800  1000                                            800
 Rated impulse withstand voltage, Uimp  [kV]  8  8                                              8
 Versions  Fixed, Plug-in (2)       Fixed, Withdrawable, Plug-in                            Fixed, Plug-in
 Breaking capacities according to IEC 60947-2  B  C  N  S  H  N  S  H  L  V              N              S
 Rated ultimate short-circuit breaking capacity, Icu
 Icu @ 250V (DC) 2-pole in series  [kA]  18  25  36  50  70  36  50  70  85  100         36            50
 Icu @ 500V (DC) 2-pole in series  [kA]  –  –  –  –  –  –  –  –  –        –              –              –
 Icu @ 500V (DC) 3-pole in series (1)  [kA]  18  25  36  50  70  36  50  70  85  100     36            50
 Icu @ 750V (DC) 3-pole in series  [kA]  –  –  –  –  –  –  –  –  –        –              –              –
 Rated service short-circuit breaking capacity, Ics
 Ics @ 250V (DC) 2-pole in series  [kA]  100%  100%  100%  100%  75%  100%  100%  100%  100%  100%  100%  75%
 Ics @ 500V (DC) 2-pole in series  [kA]  –  –  –  –  –  –  –  –  –        –              –              –
 Ics @ 500V (DC) 3-pole in series  (1)  [kA]  100%  100%  100%  100%  75%  100%  100%  100%  100%  100%  100%  75%
 Ics @ 750V (DC) 3-pole in series  [kA]  –  –  –  –  –  –  –  –  –        –              –              –
 Utilization Category (IEC 60947-2)  A       A                                                  A
 Reference Standard  IEC 60947-2          IEC 60947-2                                        IEC 60947-2
 Insulation behaviour                                                                         
 Mounted on DIN rail  DIN EN 50022       DIN EN 50022                                       DIN EN 50022
 Mechanical life  [No. Operations]  25,000  25,000                                            25,000
 [No. Hourly operations]  240               240                                                240
 Dimensions
 Fixed  3 poles  [mm]  76.2 x 70 x 130   90 x 82.5 x 130                                    105 x 70 x 150
 (Width x Depth x Height)    4 poles  [mm]  101.6 x 70 x 130  120 x 82.5 x 130              140 x 70 x 150
 Trip units for power distribution
 TMD/TMA                                     
 TMD/TMF                                                                                       
 MF/MA                                                                                         
 Trip units with low magnetic (TMG)
 TMG                                                                                           
 Interchangeable trip units                  
 Weight
 Fixed                                                                                    3/4 poles  [kg]  1.1 / 1.4  1.2 / 1.6  1.7 / 2.1
 Plug in (EF terminals)                                                           3/4 poles  [kg]  2.21 / 2.82  2.54 / 3.27  3.24 / 4.1
 Withdrawable (EF terminals)                                              3/4 poles  [kg]  3.32 / 4.04
 (1)  XT1: a 4 poles in series connection is required to be used in 500 V DC installations.              (2)  XT1 plug-in In max=125A