Page 28 - SACE Tmax XT - Catalogue
P. 28

2/10             SACE TMAX XT LOW VOLTAGE MOLDED CASE CIRCUIT-BREAKERS



          —

          SACE Tmax XT automatic circuit-breakers for

          direct current (DC) distribution











          Size                                                                         XT1                                                                         XT2                                                XT3
          Rated uninterrupted current                          [A]                     160                                                                         160                                                250
          Poles                                               [No.]                    3, 4                                                                         3, 4                                               3, 4
          Rated service voltage, Ue  (DC)                      [V]                     500                                                                         500                                                500
          Rated insulation voltage, Ui  (DC)                   [V]                     800                                                                         1000                                               800
          Rated impulse withstand voltage, Uimp               [kV]                      8                                                                           8                                                  8
          Versions                                                                 Fixed, Plug-in (2)                                                      Fixed, Withdrawable, Plug-in                            Fixed, Plug-in
          Breaking capacities according to IEC 60947-2                B        C        N        S        H                            N              S             H              L             V              N              S
          Rated ultimate short-circuit breaking capacity, Icu
          Icu @ 250V (DC) 2-pole in series                    [kA]    18       25       36       50       70                           36            50             70            85             100            36            50
          Icu @ 500V (DC) 2-pole in series                    [kA]    –        –        –        –        –                            –              –             –              –             –              –              –
          Icu @ 500V (DC) 3-pole in series (1)                [kA]    18       25       36       50       70                           36            50             70            85             100            36            50
          Icu @ 750V (DC) 3-pole in series                    [kA]    –        –        –        –        –                            –              –             –              –             –              –              –
          Rated service short-circuit breaking capacity, Ics
          Ics @ 250V (DC) 2-pole in series                    [kA]   100%     100%     100%     100%     75%                          100%          100%           100%          100%           100%          100%            75%
          Ics @ 500V (DC) 2-pole in series                    [kA]    –        –        –        –        –                            –              –             –              –             –              –              –
          Ics @ 500V (DC) 3-pole in series (1)                [kA]   100%     100%     100%     100%     75%                          100%          100%           100%          100%           100%          100%            75%
          Ics @ 750V (DC) 3-pole in series                    [kA]    –        –        –        –        –                            –              –             –              –             –              –              –
          Utilization Category (IEC 60947-2)                                            A                                                                           A                                                  A
          Reference Standard                                                        IEC 60947-2                                                                  IEC 60947-2                                        IEC 60947-2
          Insulation behaviour                                                                                                                                                                                       
          Mounted on DIN rail                                                       DIN EN 50022                                                                DIN EN 50022                                       DIN EN 50022
          Mechanical life                             [No. Operations]                25,000                                                                      25,000                                             25,000
                                                 [No. Hourly operations]               240                                                                         240                                                240
          Dimensions
          Fixed                    3 poles                    [mm]                  76.2 x 70 x 130                                                             90 x 82.5 x 130                                    105 x 70 x 150
          (Width x Depth x Height)    4 poles                 [mm]                 101.6 x 70 x 130                                                            120 x 82.5 x 130                                    140 x 70 x 150
          Trip units for power distribution
          TMD/TMA                                                                                                                                                   
          TMD/TMF                                                                                                                                                                                                     
          MF/MA                                                                                                                                                                                                       
          Trip units with low magnetic (TMG)
          TMG                                                                                                                                                                                                         
          Interchangeable trip units                                                                                                                                
          Weight
          Fixed                                                                                    3/4 poles  [kg]  1.1 / 1.4                                     1.2 / 1.6                                          1.7 / 2.1
          Plug in (EF terminals)                                                           3/4 poles  [kg]  2.21 / 2.82                                          2.54 / 3.27                                        3.24 / 4.1
          Withdrawable (EF terminals)                                              3/4 poles  [kg]                                                               3.32 / 4.04
          (1)  XT1: a 4 poles in series connection is required to be used in 500 V DC installations.              (2)  XT1 plug-in In max=125A
   23   24   25   26   27   28   29   30   31   32   33