Page 30 - SACE Tmax XT - Catalogue
P. 30

2/12             SACE TMAX XT LOW VOLTAGE MOLDED CASE CIRCUIT-BREAKERS



          —

          SACE Tmax XT automatic circuit-breakers for

          direct current (DC) distribution











          Size                                                                         XT4                                                                       XT5                                                XT6
          Rated uninterrupted current                          [A]                   160 / 250                                                                 400 / 630                                            800
          Poles                                               [No.]                    3, 4                                                                      3, 4                                               3, 4
          Rated service voltage, Ue  (DC)                      [V]                     750                                                                       750                                                750
          Rated insulation voltage, Ui  (DC)                   [V]                     1000                                                                     1,000                                              1,000
          Rated impulse withstand voltage, Uimp               [kV]                      8                                                                         8                                                  8
          Versions                                                             Fixed, Withdrawable, Plug-in                                              Fixed, Withdrawable, Plug-in                         Fixed, Withdrawable
          Breaking capacities according to IEC 60947-2               N       S      H       L      V       X                         N           S          H           L          V          X          N           S          H
          Rated ultimate short-circuit breaking capacity, Icu
          Icu @ 250V (DC) 2 poles in series                   [kA]   36     50      70      85     100    100                        25         35          50         70         85         100         35         50          70
          Icu @ 500V (DC) 2 poles in series                   [kA]   36     50      70      85     100    100                        25         35          50         70         85         100         20         35          50
          Icu @ 500V (DC) 3 poles in series                   [kA]   36     50      70      85     100    100                         -          -          -           -          -          -           -          -          -
          Icu @ 750V (DC) 3p in series                        [kA]   -       -       -      -      50      70                         -          -          -           -         85         100         18         24          36
          Rated service short-circuit breaking capacity, Ics
          Ics @ 250V (DC) 2 poles in series                   [kA]  100%   100%    100%   100%    100%    100%                      100%       100%        100%       100%       100%        100%       100%     50% (35kA)    50%
          Ics @ 500V (DC) 2 poles in series                   [kA]  100%   100%    100%   100%    100%    100%                      100%       100%        100%       100%       100%        100%       100%        50%        50%
          Ics @ 500V (DC) 3 poles in series                   [kA]  100%   100%    100%   100%    100%    100%                        -          -          -           -          -          -           -          -          -
          Ics @ 750V (DC) 3 poles in series                   [kA]   -       -       -      -     100%    100%                        -          -          -           -        100%        100%       100%        75%        50%
          Utilization Category (IEC 60947-2)                                            A                                                                         A                                                  A
          Reference Standard                                                        IEC 60947-2                                                               IEC 60947-2                                        IEC 60947-2
          Insulation behaviour                                                                                                                                                                                     
          Mounted on DIN rail                                                       DIN EN 50022                                                                  -                                                  -
          Mechanical life                             [No. Operations]                25,000                                                                    20,000                                             20,000
                                                 [No. Hourly operations]               240                                                                       120                                                120
          Dimensions
          Fixed                    3 poles                    [mm]                 105 x 82.5 x 160                                                          140 x 103 x 205                                    210 x 103.5 x 268
          (Width x Depth x Height)    4 poles                 [mm]                 140 x 82.5 x 160                                                          186 x 103 x 205                                   280 x 103.5 x 268
          Trip units
          TMD/TMA                                                                                                                                                                                                  
          TMD/TMF
          MF/MA                                                                         
          Trip units with low magnetic (TMG)
          TMG                                                                                                                                                     
          Interchangeable trip units                                                                                                                                                                               
          Weight
          Fixed                                                                                    3/4 poles  [kg]  2.5 / 3.5                                  3.25 / 4.15                                         9.5 / 12
          Plug in (EF terminals)                                                           3/4 poles  [kg]  4.19 / 5.52                                        5.15 / 6.65                                           -
          Withdrawable (EF terminals)                                              3/4 poles  [kg]  5 / 6.76                                                    5.4 / 6.9                                         12.1 / 15.1
   25   26   27   28   29   30   31   32   33   34   35