Page 66 - SACE Tmax XT - Catalogue
P. 66

3/32             SACE TMAX XT LOW VOLTAGE MOLDED CASE CIRCUIT-BREAKERS



          —

          Ekip Touch/Hi-Touch


          Overview









                           Watchdog
                           All the Ekip Touch/Hi-Touch trip units for the   Ekip Touch/Hi-Touch also features self-protec-
                           Tmax XT ensure high reliability thanks to an elec-  tion, which ensures the correct operation of the
                           tronic circuit that periodically checks the continu-  unit in overtemperatures (OT) inside the protec-
                           ity of the internal connections, such as the trip   tion trip unit.
                           coil, rating plug and each current sensor (ANSI   The following indications or controls are available:
                           74). In the event of an alarm, a message is shown   •  “Warning” LED for temperature below -20 °C or
                           on the display, and if it is set during the installa-  above +70 °C, at which point the trip unit oper-
                           tion phase, the trip unit can command the open-  ates correctly with the display switched off.
                           ing of the circuit-breaker. If a protection function   •  “Alarm” LED for temperature outside the oper-
                           intervenes, Ekip Touch/Hi-Touch always checks   ating range, at which point the trip unit com-
                           that the circuit-breaker has been opened by auxil-  mands the opening of the circuit-breaker (if set
                           iary contacts that indicate the position of the   during the configuration phase).
                           main contacts. Otherwise, Ekip Touch/Hi-Touch
                           indicates an alarm (ANSI BF code Breaker Failure)
                           to command the opening of the circuit-breaker
                           upstream.
   61   62   63   64   65   66   67   68   69   70   71