Page 71 - SACE Tmax XT - Catalogue
P. 71
PROTECTION TRIP UNITS 3/37
03
ABB Code ANSI Code Function Ekip Touch LSI Ekip Touch LSIG Ekip Touch Ekip Touch Ekip Hi-Touch LSI Ekip Hi-Touch LSIG Ekip M Touch LRIU Ekip G Touch LSIG Ekip G Hi-Touch LSIG
Measuring LSI Measuring LSIG
Frequency Protection package
UF 81L Underfrequency ● ● ● ● ●
OF 81H Overfrequency ● ● ● ● ●
UF2 81L 2nd Underfrequency ● ● ● ●
OF2 81H 2nd Overfrequency ● ● ● ●
Power Protection package
RP 32R Reverse active power ● ● ● ● ●
Cos ϕ 78 Power Factor ● ● ● ● ●
D 67 Directional overcurrent ● ● ● ●
RQ 40/32R Loss of field or reverse ● ●
reactive power
OQ 320F Reactive overpower ● ●
OP 320F Active overpower ● ●
UP 32LF Active underpower ● ●
ROCOF Protection package
ROCOF 81R Rate of change of ●
frequency
Adaptive Protection package
Set A-B Dual Setting ● ● ● ●
Motor Protection
L Motor protection ●
overload
R 51LR Rotor bloackage ●
U 46 Phase lackand/or ●
unbalance
Uc 37 Undercurrent ●
Protection with additional modules
SC 25 Synchrocheck ● ● ● ● ● ● ● ● ●
Ekip CI Motor contactor ●
interface protection
PTC PTC for temperature ●
G ext 50G TD/86/51G Earth fault ● (1) ● (1) ● (1) ● (1) ● (1)
Rc 64 50N TD 87N Residual current / ● (1) ● (1) ● (1) ● (1) ● (1) ● (1)
Differential ground
fault
● Available
Available as software package to be ordered via ABB Ability Marketplace TM or during the circuit-breaker ordering phase. To add this function, the Measuring package
must be installed first.
Note:
1) Available with additional module for XT7 and XT7 M only