Page 71 - SACE Tmax XT - Catalogue
P. 71

PROTECTION TRIP UNITS                                                            3/37



















                                                                                                                       03

 ABB Code  ANSI Code  Function  Ekip Touch LSI  Ekip Touch LSIG  Ekip Touch   Ekip Touch   Ekip Hi-Touch LSI  Ekip Hi-Touch LSIG  Ekip M Touch LRIU  Ekip G Touch LSIG  Ekip G Hi-Touch LSIG
 Measuring LSI  Measuring LSIG
 Frequency Protection package
 UF  81L  Underfrequency   ●                ●                ●                ●                ●
 OF  81H  Overfrequency    ●                ●                ●                ●                ●
 UF2  81L  2nd Underfrequency  ●            ●                ●                                 ●
 OF2  81H  2nd Overfrequency  ●             ●                ●                                 ●
 Power Protection package
 RP  32R  Reverse active power  ●           ●                ●                ●                ●
 Cos ϕ  78  Power Factor   ●                ●                ●                ●                ●
 D  67  Directional overcurrent  ●          ●                ●                                 ●
 RQ   40/32R  Loss of field or reverse                                        ●                ●
 reactive power
 OQ   320F  Reactive overpower                                                ●                ●
 OP  320F  Active overpower                                                   ●                ●
 UP   32LF  Active underpower                                                 ●                ●
 ROCOF Protection package
 ROCOF   81R  Rate of change of                                                                ●
 frequency
 Adaptive Protection package
 Set A-B  Dual Setting     ●                ●                ●                                 ●
 Motor Protection
 L  Motor protection                                         ●
 overload
 R  51LR   Rotor bloackage                                   ●
 U   46  Phase lackand/or                                    ●
 unbalance
 Uc  37   Undercurrent                                       ●
 Protection with additional modules
 SC   25  Synchrocheck   ●    ●    ●    ●  ●  ●              ●                ●                ●
 Ekip CI  Motor contactor                                    ●
 interface protection
 PTC  PTC for temperature                                    ●
 G ext  50G TD/86/51G  Earth fault  ●  (1)  ●  (1)  ●  (1)                    ●  (1)           ●  (1)
 Rc  64 50N TD 87N  Residual current /   ●  (1)  ●  (1)  ●  (1)  ●  (1)       ●  (1)           ●  (1)
 Differential ground
 fault
 ●  Available
   Available as software package to be ordered via ABB Ability Marketplace TM  or during the circuit-breaker ordering phase. To add this function, the Measuring package
       must be installed first.
 Note:
 1) Available with additional module for XT7 and XT7 M only
   66   67   68   69   70   71   72   73   74   75   76