Page 69 - SACE Tmax XT - Catalogue
P. 69

PROTECTION TRIP UNITS                                                            3/35



















                                                                                                                       03


















 ABB Code  ANSI Code  Function  Ekip Touch LSI  Ekip Touch LSIG  Ekip Touch Measuring   Ekip Touch Measuring   Ekip Hi-Touch LSI  Ekip Hi-Touch LSIG  Ekip M Touch LRIU  Ekip G Touch LSIG  Ekip G Hi-Touch LSIG
 LSI      LSIG
 Default Protection
 L  49  Overload  ●  ●  ●  ●  ●             ●                                 ●                ●
 S  50 TD / 68 / 51  Selective short circuit  ●  ●  ●  ●  ●  ●  ●             ●                ●
 I  50  Instantaneous short-  ●  ●  ●  ●  ●  ●               ●                ●                ●
 circuit
 G  50N/50N TD/68/51N  Earth Fault  ●  ●    ●                ●                ●                ●
 N  Neutral  ●  ●  ●  ●    ●                ●                                 ●                ●
 2I  50  2nd instantaneous   ●  ●  ●  ●  ●  ●                ●                ●                ●
 short-circuit
 MCR  Closing on short-circuit ●  ●  ●  ●  ●  ●              ●                ●                ●
 Iinst  Instantaneous high   ●  ●  ●  ●  ●  ●                ●                ●                ●
 intensity short-circuit
 protection
 IU  46  Current unbalance  ●  ●  ●  ●  ●   ●                ●                ●                ●
 Harmonic Distortion  ●  ●  ●  ●  ●         ●                ●                ●                ●
 T  Temperature  ●  ●  ●  ●  ●              ●                ●                ●                ●
 Hardware trip  ●  ●  ●  ●  ●               ●                ●                ●                ●
 Current Thresholds  ●  ●  ●  ●  ●          ●                ●                ●                ●
 S2  50 TD/68  2nd Time delayed   ●  ●  ●  ●  ●  ●           ●                ●                ●
 overcurrent
 Voltage Protection package
 Phase Sequence  47  Cyclical direction of the   ●  ●        ●                ●                ●
 phases
 UV  27  Undervoltage      ●                ●                ●                ●                ●
 OV  59  Overvoltage       ●                ●                ●                ●                ●
 UV2  27  2nd Undervoltage  ●               ●                ●                                 ●
 OV2  59  2nd Overvoltage  ●                ●                ●                                 ●
 VU  47  Voltage unbalance  ●               ●                ●                ●                ●
 Voltage Protection Advanced package
 S(V)  51V  Voltage controlled                                                ●                ●
 overcurrent
 S(V) 2nd  51V  2nd  Voltage controlled                                                        ●
 overcurrent
 RV  59N  Residual overvoltage                                                ●                ●
 ●  Available as standard
   Available as software package to be ordered via ABB MarketplaceTM or during the circuit-breaker ordering phase. To add this function, the Measuring package