3/44             SACE TMAX XT LOW VOLTAGE MOLDED CASE CIRCUIT-BREAKERS



          —

          Ekip Touch/Hi-Touch


          Protection functions

             Distorted waveform:
             Base + 3rd Harmonic
          240 V
          0 V
            3rd Harmonic
          -240 V
            (150 Hertz)
              Base Sine Waveform
              (50 Hertz)
             Distorted waveform:   Adaptive protection: dual setting of protections (Set A-B)
             Base + 3rd Harmonic
                           The Ekip Hi-Touch can store a set of alternative parameters (set B) for all protections. This second set
          240 V
                  Set B    can replace the default series (set A) with an external control. A typical application for dual settings may
          0 V
            3rd Harmonic   be when an emergency source is activated in the system, causing a change of load capacity and short-
          -240 V  Set A
            (150 Hertz)
              Base Sine Waveform   circuit levels, and in cases of switchgear maintenance to protect the operator against electric arcs (the
              (50 Hertz)
              Trigger event  minimum trip delays of set B guarantee safety for the operator).
                           It is possible to activate series B by:
          t     IEC 60947-4-1  •  Digital input, available with an Ekip Signalling module;
                  Set B
                Table 2    •  Communication network, by means of one of the Ekip Com communication modules;
             Set A         •  Directly from the Ekip Hi-Touch display;
                           •  Using a settable internal time, after the circuit-breaker has closed.
              Trigger event
             Distorted waveform:
             Base + 3rd Harmonic
                       I
          240 V            L Motor protection overload in compliance with Standard IEC 60947-4-1 Table 2
          t     IEC 60947-4-1
          t 0 V  Table 2   The L function protects the motor against overloads in accordance with the indications and classes
          -240 V  3rd Harmonic   defined by Standard IEC 60947-4-1 and the Table 2. The trip time is established by choosing the
            (150 Hertz)
              Base Sine Waveform   appropriate trip class, which depends on the motor that must be protected. In addition to this
              (50 Hertz)
                  Ij/Is
                           protection, the thermal memory function (implemented in accordance with Standard IEC60255-8 and
                   ti/tj  I  the above-mentioned Standard) is permanently activated. After tripping the Ekip M Touch LRIU, the
                       f   thermal memory is active for a time that depends on the trip class selected (see table).
                  Set B
          t                The protection unit will trip faster than the time established for a cold fault condition if a new overload
             Set A
                           occurs before the thermal memory automatically resets (hot trip condition). The protection has a
          t                “start-up” stage from the moment the current exceeds 0.25xIn to the moment the minimum time of the
                  Ij/Is
              Trigger event  selected trip class is reached.
                   ti/tj
                  Iu
          t     IEC 60947-4-1  f  TRIP CLASS    CLASS MIN            CLASS MAX            TMEM RESETTING TIME
                Table 2  tu  5E                 3s                   5s                   5 min
                       f   10E                  5s                   10s                  10 min
          t
                           20E                  10s                  20s                  20 min
          t                30E                  20s                  30s                  33 min
                  Iu   I
                           R Protection against rotor blockage
          t       Iuc tu   This protects the motor in two different ways, depending on whether the fault occurs on startup or
                       f
                   tuc     during normal operation. The behavior in the two operating conditions is defined by the Standard IEC
                  Ij/Is  f  947-4-1 in Annex 2. In the first case (Jam), the operation of the R function protects the motor against
          t                rotor jamming during normal operation. The R (Jam) protection function works in conjunction with the L
                   ti/tj   protection to ensure that the motor start-up phase is completed. The R (Jam) protection is inhibited
          t            f   during the start-up phase for the same time as the minimum time in the selected overload protection trip
                  Iuc
                           class. Once this time has elapsed, the R protection is activated and causes the circuit-breaker to trip if
          t       I7 tuc   the current remains above the current threshold setting (I5) for longer than the time (t5) setting of the
                       f   protection. In the second case (Stall), the protection is designed to operate to protect the motor against
                    t7     rotor jamming upon start-up. If activated, the R (Stall) protection is not inhibited during start-up and
                  Iu   f
          t                causes the circuit-breaker to open if the current remains above the current threshold setting (I8) for
                    tu     longer than the time setting (t8) of that protection. The protection has a “start-up” stage from the
          t            f   moment the current exceeds 0.25xIn to the moment the minimum time of the selected trip class is
                  I7       reached.
          t       PT100
                    t7
                       f
                       f
                  Iuc
          t
                   tuc
              Ekip M Touch LRIU  f
                  PT100
          t            f

              Contactor
                  I7
              Ekip M Touch LRIU
                    t7
                       f

          t
              Contactor

                  PT100

                       f



              Ekip M Touch LRIU




              Contactor