PROTECTION TRIP UNITS                                                            3/49



















                                                                                                                       03
                           Zone Selectivity                            Protection blocks
                           The function allows multiple circuit-breakers be-  With the Ekip Connect software six blocks are
                           longing to the same installation to be connected   available for some protections, which is useful for
                           together, in order to coordinate the trip units and   deactivating the protection based on program-
                           to reduce the tripping times in the case of protec-  mable events. In particular:
                           tions S, G, S2 and I. Thus, in the event of a failure:  •  four blocks are associated with the
                           • the circuit-breaker closest to the fault trips  programmable states A, B, C and D
                           • the other circuit-breakers are locked for a   •  one block is associated with the start-up (present
                              programmable time.                        for protections that have a StartUp function);
                           Each circuit-breaker that detects a fault reports it   •  one block, not present for frequency
                           to the circuit-breaker upstream; the circuit-breaker         protections, is associated with the checking
                           that detects the fault but does not receive any        the measured frequency.
                           communication from those downstream opens   Each block is independent and has its own activa-
                           without waiting for the set delay to elapse.  tion command. The protection is deactivated for
                           It is possible to enable zone selectivity if a fixed-  a time equal to the duration of the event itself:
                           time curve has been selected and the auxiliary  •  if the programmed event occurs (true), in the
                           supply is present.                           case of state-based blocks
                                                                       •  if the StartUp function is active and the start-up
                                                                        threshold is exceeded (the active block for the
                           StartUp Enable                              •  set start-up time), whenever the
                           The function modifies the threshold of the pro-  StartUp block function is enabled.
                           tection for a period that can be set by the user,   •  if at least one frequency measured is outside
                           avoiding unwanted trips due to high inrush cur-  the range 30…80 Hz, in the case of a frequency
                           rents of certain loads (motors, transformers,   based block.
                           lamps). The starting phase lasts 100ms to 30s
                           and is recognized automatically by the trip unit:  Directional Zone Selectivity
                           •  at the closing of the circuit-breaker with a    The Zone Selectivity function allows multiple cir-
                             self-supplied trip unit;                  cuit-breakers belonging to the same installation
                           •  when the peak value of the maximum current    to be connected together in order to coordinate
                             exceeds the set threshold (0.1…10 x In) with an    the trip units and reduce tripping times, but with
                             externally supplied trip unit.            some important differences:
                           A new start-up is possible after the current falls   •  it is to be used in installations with a ring circuit
                           below the threshold. This function can be acti-  •  it allows tripping to be managed and
                           vated with a fixed time protection function (t = k).     coordinated according to the power flows
                           Moreover, the I3 startup threshold must be higher     (determined by the direction of the current), in
                           than the I2 startup threshold.                order to minimize dispersion of energy.
                                                                       It works as an alternative to S and G Zone Selec-
                                                                       tivity.