3/48             SACE TMAX XT LOW VOLTAGE MOLDED CASE CIRCUIT-BREAKERS



          —

          Ekip Touch/Hi-Touch


          Additional protection functions









                           Additional protection functions:

                           Protection  Thermal     Trip Enable  Zone       StartUp     Blocks      Directional
                                       memory                  Selectivity  enable                 Zone Selectivity
                           L           ●
                           S           ●           ●           ●           ●           ●
                           I                                   ●           ●           ●
                           G                       ●           ●           ●           ●
                           MCR                                                         ●
                           IU                      ●
                           T                       ●
                           S2                      ●           ●           ●           ●
                           D                                               ●                       ●
                           UV                      ●                       ●
                           OV                      ●                       ●
                           VU                      ●                       ●
                           UF                      ●                       ●
                           OF                      ●                       ●
                           RP                      ●                       ●
                           S(V)                    ●                       ●
                           S2(V)                   ●                       ●
                           RV                      ●                       ●
                           RQ                      ●                       ●
                           RQ2                     ●                       ●
                           OQ                      ●                       ●
                           OP                      ●                       ●
                           UP                      ●                       ●
                           ROCOF                                           ●
                           UV2                     ●                                   ●
                           OV2                     ●                                   ●
                           UF2                     ●                                   ●
                           OF2                     ●                                   ●
                           UP                      ●
                           Gext                    ●           ●



                           Thermal memory                              Trip Enable
                           This function is used to protect components   The function enables the trip to be excluded so
                           such as transformers and cables against over-  that only the alarm is indicated. This is used in
                           heating due to overloads. It adjusts the trip time   installations where continuity of service is an
                           of the protection according to the time elapsed   essential requirement.
                           after the first overload, taking account of the
                           overheating caused. It can be activated when a
                           t = k/l  (with an inverse long time) curve is used.