3/52             SACE TMAX XT LOW VOLTAGE MOLDED CASE CIRCUIT-BREAKERS



          —

          Ekip Touch/Hi-Touch


          Protection settings










          ABB Code     ANSI Code  Function                      Threshold Range              Threshold Step                      Trip Time                       Time Step    Excludability  Excludability trip Pre-Allarm  Curve
          Protections
          S2(V)        51V        2nd  Voltage controlled overcurrent   I21 = 0.6...10 x In  0.1 x In                            t21 = 0.05…30 s                 0.01 s       yes           yes          no              t = k
                                  Step mode (controlled mode)   Ul2 = 0.2…1 x Un             0.01 x Un
                                                                Ks2 = 0.1…1                  0.01
                       51V        Linear mode (restrained mode)  Ul2 = 0.2…1 x Un            0.01 x Un
                                                                Uh2 = 0.2…1 x Un             0.01 x Un
                                                                Ks2 = 0.1…1                  0.01
          RV           59N        Residual overvoltage          U22 = 0.05….0.5 x Un         0.001 x Un                          t22 = 0.5…120 s                 0.01 s       yes           yes          no              t = k
          UF           81L        Underfrequency                f12 = 0.9….0.999 fn          0.001 x fn                          t12 = 0.15…300 s                0.01 s       yes           yes          no              t = k
          OF           81H        Overfrequency                 f13 = 1.001….1.1 fn          0.001 x fn                          t13 = 0.15…300 s                0.01 s       yes           yes          no              t = k
          UF2          81L        2nd Underfrequency            f17 = 0.9….0.999 fn          0.001 x fn                          t17 = 0.15…300 s                0.01 s       yes           yes          no              t = k
          OF2          81H        2nd Overfrequency             f18 = 1.001….1.1 fn          0.001 x fn                          t18 = 0.15…300 s                0.01 s       yes           yes          no              t = k
          RP           32R        Reverse active power          P11 = -1…-0.05 Sn            0.001 Sn                            t11 = 0.5…100 s                 0.1 s        yes           yes          no              t = k
          Cos ϕ        78         Power factor                  Cos φ = 0.5…0.95             0.01                                                                             yes           only signaling  no
          D            67         Directional overcurrent       I7 Fw/Bw = 0.6...10 x In     0.1 x In                            t7 Fw/Bw = 0.2...0.8 s          0.01 s       yes           yes          no              t = k
                       68         Zone selectivity                                                                               t7sel = 0.13…0.5s               0.01 s       yes
                                  Start up                      Activation: 0.6…10 x In      0.1 x In                            Range 0.1…0.8s                  0.01 s       yes
                                  Minimum angle of direction (°)  3.6, 7.2, 10.8, 14.5, 18.2, 22,
                                                                 25.9, 30, 34.2, 38.7, 43.4, 48.6,
                                                                 54.3, 61, 69.6
          RQ           40/32R     Loss of field or reverse reactive power  Q24 = -1…-0.1 x Sn  0.001 x Sn                        t24 = 0.5…100 s                 0.1 s        yes           yes          no              t = k
                                                                Kq = -2…2                    0.01
                                  Loss of field or reverse reactive power  Q25 = -1…-0.1 x Sn  0.001 x Sn                        t24 = 0.5…100 s                 0.1 s        yes           yes          no              t = k
                                                                Kq = -2…2                    0.01
                                  Minimum voltage threshold     Vmin. = 0.5…1.2              0.01                                                                             yes
          OQ           320F       Reactive overpower            Q27 = 0.4…2 x Sn             0.001 x Sn                          t27 = 0.5…100 s                 0.5 s        yes           yes          no              t = k
          OP           320F       Active overpower              P26 = 0.4…2 x Sn             0.001 x Sn                          t26 = 0.5…100 s                 0.5 s        yes           yes          no              t = k
          UP           32LF       Active underpower             P23 = 0.1...1 x Sn           0.001 x Sn                          t23 = 0.5…100 s                 0.5 s        yes           yes          no              t = k
                                  StartUp                                                                                        Range from closing: 0.1…30S or with digital   0.01 s  yes                               -
                                                                                                                                 input
          ROCOF        81R        Rate of change of frequency   f28 = 0.4…10 Hz / s (up &/or down)  0.2 Hz/s                     t28 = 0.5...10 s for f>f28      0.01 s       yes           yes          no              t = k
          L (Motor     49         Motor protection overload     I1 = 0.4…1 x In              0.001 x In                          XT2-XT4: 5E - 10E - 20E                                                                 t = k/I  2
          Protection)             According 60947-4-1                                                                            XT5-XT7: 5E - 10E - 20E - 30E
          R            51R        Rotor blockage  - Jam         Ij = 2…10 x I1               0.1                                 tj = 1…10 s                     0.5 s                                                   t = k
                       51R        Rotor blockage - Stall        Is = 1…10 x I1               0.1                                 ts = 2…10 s                     0.5 s                                                   t = k
          U                       Phase lackand/or unbalance    On/Off                       -                                   tu = 1…10 s                     0.5 s                                                   t = k
          Uc           37         Undercurrent                  50…90% x I1                  10%                                 tuc = 1…20 s                    0.5 s                                                   t = k
          Protection with additional modules
          SC           25         Synchrocheck                  Ulive = 0.5…1.1 x Un         0.001 x Un                          Stability voltage time          0.001 s      yes           only signaling  no
          Synchrocheck            (Live busbars)                ΔU = 0.02…0.12 x Un          0.001 x Un                          for live state = 100…30000ms    0.01 s
                                                                Δf = 0.1…1 x Hz              0.1 x Hz                            Minimum matching time =
                                                                Δ� 5…50° elt                 5° elt                              100…3000ms
                                  Synchrocheck                  Ulive = 0.5…1.1 x Un         0.001 x Un                          tref = 0.1…30 s                 0.1 s        yes           only signaling  no
                                  (Live. Dead busbars)          Udead = 0.02…0.2 x Un        0.001 x Un
                                  Frequency check off                                                                                                                         yes
                                  Phase check off                                                                                                                             yes
                                  Dead bar configuration        Reverse/Standard                                                                                              yes
                                  Primary voltage               100…1150                     100, 115, 120, 190, 208,
                                                                                             220, 230, 240, 277, 347,
                                                                                             380, 400, 415, 440, 480,
                                                                                             500, 550, 600, 660, 690,
                                                                                             910, 950, 1000, 1150
                                  Secondary voltage             100…120                      100, 110, 115, 120
          Gext         50G TD     Earth fault                   I41  = 0.1…1 x In toroid     0.001 x In toroid                   t4 = 0.1…1 s                    0.05 s       yes           yes          50…90% I41 step 1%  t = k
                                                                   (1)
                       68         Zone selectivity                                                                               t41sel = 0.04…0.2 s             0.01 s       yes
                                  Start up                      Activation: 0.1…1 x In       0.02 x In                           Range: 0.1…30s                  0.01 s       yes
                                                                   (1)
                       51G        Earth fault                   I41  = 0.1…1 x In            0.001 x In                          t4 = 0.1…1 s with I = 4 x In    0.05 s       yes           yes          50…90% I41 step 1%  t = k/I  2
          MDGF  (2)               Earth fault                   I41 = 0.1...1 x In toroid    0.001 x In toroid                   t41 = 0.05…0.4 s                0.05 s       yes           yes          50...90% I41 step 1%  t = k
                                                                Max setting 1200A
                                  Earth fault                   I41 = 0.1...1 x In           0.001 x In                          t41 = 0.1…0.4 s                 0.05 s       yes           yes          50...90% I41 step 1%  t = k/I  2
          Rc           64 50N TD 87N Residual current / Differential ground fault  IΔn = 3 - 5 - 7 - 10 – 20 – 30A               tΔn = 0.06 – 0.1 – 0.2 – 0.3 – 0.4 – 0.5 – 0.8 s           no           no              t = k
          All the protection functions can be excluded if needed except for L. I. MCR. The RC for the XT7 is active only when the rating plug is present. All of the Synchrocheck functions are for signaling.
          An adjustable pre-alarm threshold (50...90% l1) is available for L protection, as well as a fixed pre-alarm threshold is available for G and Gext protection.
          (1) With Vaux all thresholds are available. Without Vaux there are minimum threshold limitations. Details available on the "User manual for use and maintenance of Ekip Touch Trip units"
          (2) Available for XT7 only.