Page 95 - SACE Tmax XT - Catalogue
P. 95

PROTECTION TRIP UNITS                                                            3/61



















                                                                                                                       03

 Network Analyzer  Interval  Ekip Touch  Ekip Touch Measuring  Ekip Hi-Touch  Ekip M Touch   Ekip G Touch   Ekip G Hi-Touch
 Hourly average voltage value  [V] [no] - Umin= 0.75…0.95 x Un  t = 5…120min        ●         ●
 - Umax= 1.05…1.25 x Un
 - Events counter  (1)
 Short voltage interruptions  [no] - Umin= 0.75…0.95 x Un  t <40ms        ●                   ●
 - Events counter  (1)
 Short voltage spikes  [no] - Umax= 1,05…1,25 x Un  t <40ms        ●                          ●
 - Events counter  (1)
 Slow voltage sags and swells  [no] - Umin1= 0.75…0.95 x Un  t = 0.02s...60s        ●         ●
 - Umin2= 0.75…0.95 x Un
 - Umin3= 0.75…0.95 x Un
 - Umax1= 1.05…1.25 x Un
 - Umax2= 1.05…1.25 x Un
 - Events counter  (1)
 Voltage unbalance  [V] [no] - U neg. seq.= 0.02…0.10 x Un  t = 5…120min        ●             ●
 - Events counter  (1)
 Harmonic analysis  Current and Voltage        ●                                              ●
 - up to 50 th
 - Alarm THD: 5…20%
 - Single harmonic alarm:
 3...10% plus a count of minutes the harmonic has been
 exceeded
 Record of values: for each interval with time-stamping  Parameters  Window & interval
 Current: minimum and maximum  [A] I Min, I Max  Fixed synchronizable   ●  ●  ●  ●  ●         ●
 Phase-to-phase voltage: minimum and maximum  [V] U Min, U max  by remote   (2)  ●  ●  ●  ●   ●
 Active power: average and maximum  [kW] P Mean, P Max  Duration: 5…120min   (2)  ●  ●  ●  ●  ●
 Reactive power: average and maximum  [kVAR] Q Mean, Q Max  Number of intervals:    (2)  ●  ●  ●  ●  ●
 Apparent power: average and maximum   [KVA] S Mean, S Max  24   (2)  ●  ●  ●  ●              ●
 Data logger: high rate sampling record of  parameters  Parameters
 Currents  [A] L1, L2, L3, Ne, Ig  Fixed synchronizable         ●            ●                ●
 Voltages  [V] U12, U23, U31  by remote        ●                             ●                ●
 Sampling rate  [Hz] 1200-9600  Duration: 5…120min        ●                  ●                ●
 Maximum recording duration  [s] 18  Number of intervals:         ●          ●                ●
 Recording stop delay  [s] 0-10s  24        ●                                ●                ●
 Number of registers  [no] 2 independent        ●                            ●                ●

 Info on trip & opening data: after a fault without auxiliary supply  Parameters
 Type of protection tripped  eg. L, S, I, G, UV, OV  ●  ●  ●  ●              ●                ●
 Fault values per phase  [A/V/Hz  eg. I1, I2, I3, neutral for S protection  ●  ●  ●  ●  ●     ●
 w/VAR] V12, V23, V32 for UV protection
 Time-stamping  Date, time and progressive number  ●  ●  ●  ●                ●                ●

 Maintenance indicators  Parameters
 Information on last 30 trips  Type of protection, fault values and time-stamping  ●  ●  ●  ●  ●  ●
 Information on last 200 events  Type of event, time-stamping  ●  ●  ●  ●    ●                ●
 Number of mechanical operations  [no] can be associated to alarm  ●  ●  ●  ●  ●              ●
 Total number of trips  [no]  ●  ●         ●                ●                ●                ●
 Total operating time  [h]  ●  ●           ●                ●                ●                ●
 Wear of contacts  [%] Pre-alarm >80%  ●  ●  ●              ●                ●                ●
 Alarm = 100%
 Date of maintenance operations performed  Last  ●  ●  ●    ●                ●                ●
 Indication of maintenance operation needed  ●  ●  ●        ●                ●                ●
 Circuit-breaker I.D.  Type of circuit-breaker, assigned device name, serial   ●  ●  ●  ●  ●  ●
 number
 Self-diagnosis  Parameters
 Check of continuity of internal connnections  Alarm due to disconnection: rating plug, sensors,   Note: Opening of the   ●  ●  ●  ●  ●  ●
 trip coil  circuit-breaker can be
 Failure of circuit-breaker to open (ANSI 50BF)  Alarm following non-tripping of protection functions  set in the event of   ●  ●  ●  ●  ●  ●
 Temperature (OT)  Pre-alarm and alarm for abnormal temperature  alarm  ●  ●  ●  ●  ●         ●
 ● Available as standard  1) No. of events day by day in the last year plus the total events in the breaker's lifetime
  Available as software package to be ordered via ABB Ability Marketplace TM  or during the circuit-breaker ordering phase. To add this function, the Measuring package must    2) Available only if Measuring package is enabled