3/56             SACE TMAX XT LOW VOLTAGE MOLDED CASE CIRCUIT-BREAKERS



          —

          Ekip Touch/Hi-Touch


          Measurement functions and data









                           Currents                                    Datalogger
                           All the Ekip Touch/Hi-Touch trip units measure   This function allows the data related to a trigger
                           the RMS value of the instantaneous currents of   event to be recorded. These data are:
                           the three phases and the neutral. There are two   •   Analog measurements: phase currents and
                           different levels of accuracy depending on the ver-  phase-to-phase voltages
                           sion  (0.5% and 1%). In addition, also the mini-  •   Digital events: protection alarms, circuit-
                           mum and maximum values recorded within an ad-  breaker status signals, tripping of protections.
                           justable time interval are available.       When the datalogger is activated, the trip unit
                                                                       continuously acquires data by filling and empty-
                           Voltage                                     ing an internal register. If a trigger event occurs,
                           Instantaneous phase-to-phase and phase-to-  the trip unit inhibits acquisition (either immedi-
                           neutral voltages can be measured. They are   ately or with an adjustable time-lag) and stores
                           available at a 0.5% level of accuracy. In addition,   the data, which is available for downloading.
                           the minimum and maximum values recorded
                           within an adjustable time interval are available.  Network Analyzer
                                                                       This function fully evaluates the quality of the
                           Power                                       network. It is possible to set the controls to long
                           Real time measurements of the total and phase   cycle voltage and current in order to analyze the
                           power. Available at 2 different level of accuracy   system functionality. Voltages and currents are
                           depending on the version, 1 % and 2%. In addi-  monitored to find:
                           tion, the minimum and maximum values recorded   •  The sequence of voltages
                           within an adjustable time interval are available.  •  Short term voltage drops or interruptions
                                                                       •  Short duration voltage increases
                           Energy meters                               •  Slow voltage drops
                           Measurements of the active, reactive and apparent   •  Slow voltage increases
                           energy totals, updated every minute. The meas-  •  Unbalances between the voltages
                           urements can be reset when needed.          •  Harmonic distortion of voltages and currents.

                           Frequency                                   Waveforms
                           Measurement of line real time frequency, ex-  A selected quantity can be represented as a wave-
                           pressed in hertz.                           form and acquired at the moment of selection.
                                                                       The phase current and phase-phase voltage can
                           Peak Factor                                 be displayed.
                           Real time measurements of the peak factors of
                           the phase currents. The measurements are ex-  Harmonics
                           pressed as a ratio between the peak values and   A representation in the form of a histogram of the
                           RMS values, for each single phase.          measurements of the harmonics that make up the
                                                                       waveform, and related to the frequency set.
                           Power Factor
                           Power factor and real time measurements of the
                           ratio between the total active power and total
                           apparent power, expressed as Cosϕ. In addition,
                           the trip unit signals an alarm if the cosϕ value
                           drops below an adjustable threshold, settable via
                           Ekip Connect software (from 0.5 to 0.95).