PROTECTION TRIP UNITS                                                            3/57



















                                                                                                                       03
                           Operation counter                           Events
                           In the presence of a power supply, the trip unit re-  The last 200 events are recorded. The following
                           cords information about the openings of the cir-  information is available:
                           cuit-breaker including:                     •  trip unit: configuration status of the bus,
                           •  the number of manual openings             operating mode, active set, auxiliary power
                           •  the total number of operations (manual + trips).  supply
                           By activating communication with the trip unit,   •  protections: delay in action or alarms
                           the following parameters are also available:  •  connection states or alarms: circuit-breaker,
                           •  the number of openings due to protection   current sensors,  trip coil, rating plug
                            tripping                                   •  tripping: state of the opening command, or
                           •  the number of openings for which tripping has   signal of tripping for protection.
                            not been completed in due time (back-up    The icons help to quickly understand the type of
                            commands have been necessary)              event:
                           •  the number of opening tests performed.      i  event reported for information purposes

                           Contact wear                                   delay of a protection in progress, trip
                           This gives an estimation of the conditions of the   expected
                           main circuit-breaker contacts. The value is ex-     !  alarm referring to a non-hazardous condition
                           pressed as a percentage, and is 0% in case of no
                           wear, and 100% in case of total wear. This is calcu-     alarm for operation, failure, or connection
                           lated automatically by the trip unit at every open-  fault.
                           ing for protection or, in the presence of a power
                           supply, also at every manual opening of the cir-  Synchrocheck
                           cuit-breaker.                               Synchrocheck measurements relating to the func-
                                                                       tion of synchronism between two independent
                           Openings                                    power sources.
                           Information about the last 30 openings are
                           available. In particular:
                           •  tripped protection
                           •  the progressive number of the opening
                           •  the date and time of the opening (referred to the
                             internal clock)
                           •  measurements associated with the
                             trip protection.
                           The most recent opening is viewable also by
                           pressing the iTest key.