Page 45 - Surge-Protection-E_0.pdf
P. 45

Coordinated Lightning Current Arresters – Type 1
                                                                                            WBF    CIRCUIT INTERRUPTION
                                                                                           DEHN-FUNKENSTRECKEN-TECHNOLOGIE INSIDE
                                                                                          WELLENBRECHER-FUNKTION  FUSE INTEGRATED
           DEHNbloc Maxi S
           • Spark-gap-based lightning current arrester with integrated
            lightning current carrying backup fuse in a compact enclosure
           • Directly mounted on the PEN / N busbar
           • Low voltage protection level UP ≤ 2.5 kV
            (including 80 cm connecting cable)
           • Directly coordinated with DEHNguard surge protective device
            without additional cable length
           • Short-circuit withstand capability of 100 kArms (220 kApeak)
           • High follow current extinguishing capability and limitation
            due to RADAX Flow technology
           • High lightning current discharge capacity
           • With optical-fibre interface for SPD monitoring

                                                                For protecting low voltage consumer installations against surges and even direct
                                                                lightning strikes. For installation in conformity with the lightning protection zone
                                                                concept at the boundaries from 0A – 1.


           DEHNbloc Maxi 1 255 S:  Coordinated lightning current arrester with integrated backup fuse for busbar installation

           DEHNbloc Maxi S can be easily integrated into the application environ-  For 3+1 configurations, DEHNgap Maxi S provides a powerful creepage
           ment of a low-voltage switchgear installation or distribution board.   discharge spark gap with a discharge capacity of 100 kA (10/350 µs).
           Thanks to its unique mechanical design, the coordinated DEHNbloc Maxi S   DEHNbloc Maxi S also features patented RADAX Flow follow current lim-  Lightning Current Arresters – Type 1
           lightning current arrester can be directly mounted on the PEN / N busbar   itation, thus ensuring selectivity even in case of low-current-rated fuses.
           of a switchgear installation without the need for additional adapters.  The ability to conduct lightning impulse currents without destruction and
           With the backup fuse integrated in the device, no other separate backup   to suppress mains follow currents without tripping upstream overcurrent
           fuses need to be installed.                          protective devices ensures the availability of the switchgear installation
           Installing DEHNbloc Maxi S directly into the connection panel of a switch-  in the event of a lightning strike. This considerably reduces the risk of arc
           gear installation upstream of the circuit breaker ensures short cable   formation in the installation.
           lengths of the arresters and a low voltage protection level for the instal-  In conjunction with the DEHNsignal remote signalling system, the oper-
           lation. In this environment, the VDE-tested DEHNbloc Maxi S can be used   ating state of DEHNbloc Maxi S devices can be monitored at any time.
           for short-circuit currents up to 100 kArms.          Easy-to-implement optical fibre transmission to the DEHNsignal E 3 re-
           With a discharge capacity of 25 kA (10/350 µs), DEHNbloc Maxi S fulfils   mote signalling receiver module ensures safe electrical isolation between
           the highest national and international lightning protection standards for   the power circuit and the remote signalling circuit.
           all three-phase current applications in TN and TT systems.



           *)  DEHNbloc Maxi S
             DBM 1 255 S
           **) DEHNgap Maxi S  main circuit breaker                        main circuit breaker
             DGPM 1 255 S
                                                    TT / TN-S
                                                    DSI E 3                                              TN-C
                                                   power supply                                          DSI E 3
                                         plastic  LWL DSI
                        L1                                                                   plastic LWL DSI  power supply
                            L2  L3      optical fibre cable                 L1  L2
                                         max.6 m      S N L                      L3         optical fibre cable
                                                                                             max.6 m      S N L
                                                  without         *)  DEHNbloc Maxi S

                                                  wire              DBM 1 255 S                       with
                                                  jumper  N L                                         wire
                                                  S/N
                     **)                                                                              jumper
                        *)                                                                            S/N  N L
                           *)                                              *)
                              *)
             N busbar                                                         *)                          (PEN)
                                                                                 *)
                                                                  PEN busbar
                                                   DEHNgap Maxi S
                                           S  N      L
                                                   DGPM 1 255 S
                   PE busbar                                                                   S  N  L
                                                   power supply     equpotential bonding
                                              F    230 V ~
                                                       L  max.16 A gL/gG                          F     power supply
              equipotential bonding
           9                  !                    N  (C 16 A)                   !                         L  max.16 A gL/gG
                                                                                                        230 V ~
                                                                                                      N
                                                                                                      (C 16 A)
                         All three optical fibre cables                      All three optical fibre cables


                           must be connected!                                must be connected!
           3+1 application in a TT / TN-S system                3-0 application in a TN-C system
           DEHNbloc Maxi 1 255 S                                                                            900 220   DBM 1 255 S
           Coordinated single-pole lightning current arrester with integrated backup fuse for busbar installation in 230 / 400 V systems.
                                                                                                            900 220   4013364106734  04 01 01 11   699 g
                                                                                                                  313,50 €
           Type                                 DBM 1 255 S
           Part No.                             900 220
           SPD according to EN 61643-11 / IEC 61643-11  type 1 / class I
           Max. continuous operating voltage (a.c.)  (UC)  255 V (50 / 60 Hz)
           Lightning impulse current (10/350 µs)  (Iimp)  25 kA
           Voltage protection level  (UP)       ≤ 2.5 kV (including 80 cm connecting cable)
           Max. mains-side overcurrent protection  not required
           Operating state indication           by optical fibre cables via DSI E 3
           Valid as of August 1, 2020                         You will find detailed product information on our website   41