Page 48 - Surge-Protection-E_0.pdf
P. 48

Coordinated Lightning Current Arresters – Type 1 for d.c. Applications

        971 126   DSE M 1 60 FM
        971 125   DSE M 1 220 FM
        971 127   DSE M 1 242 FM  DEHNsecure M 1 ... FM
                         Coordinated and modular single-pole lightning current arrester for d.c. applications;
        971 126   4013364138599  04 01 01 12   288 g
              281,40 €   with remote signalling contact for monitoring device (floating changeover contact).
        971 125   4013364133648  04 01 01 12   226 g
              310,30 €
        971 127   4013364144484  04 01 01 12   254 g
              340,10 €
                          Type DSE M ...                       1 60 FM         1 220 FM        1 242 FM
                          Part No.                             971 126         971 125         971 127
                          SPD classification according to EN 61643-11 / IEC 61643-11  type 1 / class I    type 1 / class I   type 1 / class I
                          Max. continuous operating voltage (d.c.)  (UC)  60 V  220 V          242 V
                          Lightning impulse current (10/350 µs)  (Iimp)  25 kA  25 kA          25 kA
                          Voltage protection level  (UP)       ≤ 1.5 kV        ≤ 2.5 kV        ≤ 2.5 kV
                          Max. mains-side overcurrent protection  250 A gL     250 A gL        250 A gL
                          Approvals                            UL              —               —
                          Type of remote signalling contact    changeover contact   changeover contact   changeover contact
                          Extended technical data:                         when used in safety lighting systems
                           – Max. continuous operating voltage (a.c.)  (UC)  —  —              255 V
        971 221   DSE M 2P 60
        971 226   DSE M 2P 60 FM  DEHNsecure M 2P ... (FM)
                         Coordinated and modular two-pole lightning current arrester for d.c. applications up to 60 V (1+1 configuration);
        971 221   4013364138612  04 01 01 12   608 g
              610,90 €   FM version with floating remote signalling contact.
        971 226   4013364138629  04 01 01 12   614 g
              661,00 €
                          Type DSE M ...                       2P 60           2P 60 FM
    Lightning Current Arresters – Type 1  Max. continuous operating voltage (d.c.)  (UC)  60 V  60 V
                          Part No.
                                                               971 221
                                                                               971 226
                                                                               type 1 / class I
                          SPD classification according to EN 61643-11 / IEC 61643-11
                                                               type 1 / class I
                          Lightning impulse current (10/350 µs)
                                                                               25 / 50 kA
                                                               25 / 50 kA
                               (DC+/DC-  -> DC-/DC+) / (DC-/DC+  -> 9)  (Iimp)
                          Voltage protection level
                                                                               ≤ 1.5 / ≤ 1.5 kV
                                                               ≤ 1.5 / ≤ 1.5 kV
                               (DC+/DC-  -> DC-/DC+) / (DC-/DC+  -> 9)  (UP)
                          Max. mains-side overcurrent protection
                                                               UL
                                                                               UL
                          Approvals                            250 A gL        250 A gL
                          Type of remote signalling contact    —               changeover contact
                                                                                                         WBF
                                                                                                        DEHN-FUNKENSTRECKEN-TECHNOLOGIE INSIDE
                                                                                                       WELLENBRECHER-FUNKTION
        Protection Module for DEHNsecure modular
                                              • Spark gap technology particularly suited for use in d.c. circuits
                                              • Operating state / fault indication by green / red indicator flag in the inspection
                                               window
                                              • Easy replacement of protection modules without tools due to module locking
                                               system with module release button
                                              DSE MOD ...:  Spark-gap-based protection module





                                              Avoid additional, short-notice and unplanned maintenance jobs. In multipole protective circuits,
                                              we recommend replacing the complete set of protection modules when one module fails.
        For protecting d.c. consumer installations against surges
        and even direct lightning strikes. For installation in con-
        formity with the lightning protection zone concept at the
        boundaries from 0A – 1.

        971 001   DSE MOD 60
        971 002   DSE MOD 220  DSE M Spark-Gap-Based Protection Module
        971 003   DSE MOD 242
                          Type DSE MOD ...                     60              220             242
        971 001   4013364138605  04 01 01 12   139 g
              233,50 €
        971 002   4013364133655  04 01 01 12   106 g
              263,30 €
        971 003   4013364144491  04 01 01 12   108 g
              293,20 €    Part No.                             971 001         971 002         971 003
                          Max. continuous operating voltage (d.c.)  (UC)  60 V  220 V          242 V
                          Lightning impulse current (10/350 µs)  (Iimp)  25 kA  25 kA          25 kA
                         DSE PE Spark-Gap-Based Protection Module
        971 010   DSE MOD PE 60
                          Type DSE MOD ...                     PE 60
        971 010   4013364138636  04 01 01 12   171 g
              327,30 €
                          Part No.                             971 010
                          Max. continuous operating voltage (d.c.)  (UC)  60 V
                          Lightning impulse current (10/350 µs)  (Iimp)  50 kA
        44               You will find detailed product information on our website             Valid as of August 1, 2020
   43   44   45   46   47   48   49   50   51   52   53