Page 50 - Surge-Protection-E_0.pdf
P. 50

Lightning Current Arresters – Type 1

                         DEHNbloc 1 255 H
        900 222   DB 1 255 H
                         Single-pole (3-0 configuration) lightning current arrester with a high discharge capacity for use in 230 / 400 V systems.
        900 222   4013364102521  04 01 01 13   331 g
              163,20 €
                          Type                                   DB 1 255 H
                          Part No.                               900 222
                          SPD according to EN 61643-11 / IEC 61643-11  type 1 / class I
                          Max. continuous operating voltage (a.c.)  (UC)  255 V (50 / 60 Hz)
                          Lightning impulse current (10/350 µs)  (Iimp)  50 kA
                          Voltage protection level  (UP)         ≤ 4 kV
                          Max. backup fuse up to IK = 50 kArms (ta ≤ 0.2 s)  500 A gG
                          Max. backup fuse up to IK = 50 kArms (ta ≤ 5 s)  315 A gG
                          Approvals                              KEMA



                         DEHNbloc 3 255 H
        900 120   DB 3 255 H
                         Three-pole (3-0 configuration) lightning current arrester with a high discharge capacity for use in 230 / 400 V systems.
        900 120   4013364109377  04 01 01 13   873 g
              462,00 €
                          Type                                   DB 3 255 H
                          Part No.                               900 120
                          SPD according to EN 61643-11 / IEC 61643-11  type 1 / class I
    Lightning Current Arresters – Type 1  Voltage protection level  (UP)  ≤ 4 kV
                                                                 255 V (50 / 60 Hz)
                          Max. continuous operating voltage (a.c.)  (UC)
                                                                 100 kA
                          Lightning impulse current (10/350 µs) [L1+L2+L3-N/PEN]  (Itotal)
                                                                 500 A gG
                          Max. backup fuse up to IK = 50 kArms (ta ≤ 0.2 s)
                                                                 315 A gG
                          Max. backup fuse up to IK = 50 kArms (ta ≤ 5 s)
                                                                 KEMA
                          Approvals

























































        46               You will find detailed product information on our website             Valid as of August 1, 2020