Page 49 - Surge-Protection-E_0.pdf
P. 49
Lightning Current Arresters – Type 1
WBF
DEHN-FUNKENSTRECKEN-TECHNOLOGIE INSIDE
WELLENBRECHER-FUNKTION
DEHNbloc
• Encapsulated non-exhausting creepage discharge spark gap
• RADAX Flow spark gap technology with high follow current
limitation
• Energy coordination with other arresters of the Red/Line
product family
• Can also be used upstream of meter panels due to its high
insulation resistance
• Multifunctional terminal for connecting conductors and busbars
• Single-pole and three-pole version (lightning impulse currents
up to 100 kA depending on the system configuration)
• Modular single-pole version also available
For protecting low-voltage consumer installations against surges and even direct
lightning strikes. For installation in conformity with the lightning protection zone
concept at the boundaries from 0A – 1.
DEHNbloc H M 1 255: Modular single-pole lightning current arrester with high follow current limitation
DEHNbloc 1 255 H: Single-pole lightning current arrester with high follow current limitation
DEHNbloc 3 255 H: Three-pole lightning current arrester with high follow current limitation
The spark gaps of the DEHNbloc lightning current arresters allow compact But the DEHNbloc H family concept also stands out due to other product Lightning Current Arresters – Type 1
configuration of low-voltage distribution boards. By using pressurised and features: With its double terminals on the phase and earth side, the sin-
encapsulated creepage discharge spark gaps, no safety distance from gle-pole DEHNbloc 1 255 H device offers various application options.
busbars and special flameproof enclosures are necessary. The DBH M 1 255 device with a new arrester design features the approved
With a lightning current discharge capacity up to 50 kA (10/350 µs) per module release system that safely fixes the protection module to the base
pole, DEHNbloc devices fulfil the highest national and international light- part even at maximum loads on the protection module. The module can
ning protection and application standards. be easily replaced without tools by simply pressing the module release
Consistent pursuit of the idea of integration has made the DEHNbloc button of the protection module.
devices even more efficient: With DEHNbloc H, the groundbreaking By using the double terminals suitable for all conductors, even three-pole
RADAX Flow spark gap technology for follow current extinction and lim- DEHNbloc 3 255 H arresters can be connected in series in a space-saving
itation was integrated into the DEHNbloc family. and cost-effective way up to nominal currents of 125 A as preferred by
The RADAX flow technology prevents interruptions in operation due to IEC 60364-5-53.
tripping of the circuit breaker when the arrester responds. In times where If DEHNbloc is to be used with other DIN rail mounted devices, the multi-
systems increasingly depend on a properly functioning electrical infra- functional terminals are ideally suited for connecting conductors and
structure, this is an indispensable product feature. Thanks to the patented busbars.
RADAX Flow principle, even the amplitude of short-circuit currents in in-
stallations up to 50 kArms can be limited to approx. 500 A and extin-
guished after approximately 5 ms. This feature ensures selectivity even in
case of low-current-rated fuses.
DEHNbloc H 961 122 DBH M 1 255
Modular single-pole lightning current arrester with a high discharge capacity for use in 230 / 400 V systems.
961 122 4013364118652 04 01 01 08 358 g
182,30 €
Type DBH M 1 255
Part No. 961 122
SPD according to EN 61643-11 / IEC 61643-11 type 1 / class I
Max. continuous operating voltage (a.c.) (UC) 255 V (50 / 60 Hz)
Lightning impulse current (10/350 µs) (Iimp) 50 kA
Voltage protection level (UP) ≤ 4 kV
Max. backup fuse (L) up to IK = 50 kArms (ta ≤ 0.2 s) 500 A gG
Max. backup fuse (L) up to IK = 50 kArms (ta ≤ 5 s) 315 A gG
Accessories for DEHNbloc
DB H Spark-Gap-Based Protection Module 961 022 DBH MOD 255
Type DBH MOD 255
961 022 4013364118669 04 01 01 08 195 g
Part No. 961 022
160,00 €
Max. continuous operating voltage (a.c.) (UC) 255 V
Valid as of August 1, 2020 You will find detailed product information on our website 45