Page 48 - V16 Catalogue Final
P. 48

SACE TMAX XT MOULDED CASE CIRCUIT BREAKERS
           TECHNICAL DATA








          Size                                                             XT1            XT2            XT3                            XT4                  XT5                 XT6 (2)              XT7                 XT7M
          Rated uninterrupted current                              [A]     160            160            250                          160 / 250            400 / 630             800 (6)        1000 / 1250 / 1600  800 / 1000 / 1250 / 1600
          Poles                                                  [No.]     3, 4           3, 4           3, 4                           3, 4                 3, 4                3, 4                 3, 4                 3, 4
                                               (AC)
          Rated service voltage, Ue                                [V]     690            690            690                            690                  690                 690                  690                  690
                                               50-60Hz
          Rated insulation voltage, Ui                             [V]     800            1000           800                            1000                1000                 1000                 1000                1000
          Rated impulse withstand voltage, Uimp                   [kV]      8              8              8                              8                    8                   8                    8                   8
                                                                                     Fixed, Withdrawable,                         Fixed, Withdrawable,   Fixed, Withdrawable,
          Versions                                                     Fixed, Plug-in (1)             Fixed, Plug-in                                                        Fixed, Withdrawable  Fixed, Withdrawable  Fixed, Withdrawable
                                                                                         Plug-in                                       Plug-in             Plug-in  (5)
          Breaking capacities according to IEC 60947-2                      N          N       H          N                         N         H         N          H         S         H          S         H         S         H
          Rated ultimate short-circuit breaking capacity, Icu
          Icu @ 220-230-240V 50-60Hz (AC)                         [kA]      65        65      100         50                        65       100        70        100        85        100       85        100        85        100
          Icu @ 415V 50-60Hz (AC)                                 [kA]      36        36       70         36                        36        70        36        70         50        70        50         70        50        70
          Icu @ 690V 50-60Hz (AC)                                 [kA]      6         10       15         5                         10        15        20        40         22        25        30         42        30        42
          Rated service short-circuit breaking capacity, Ics
          Ics @ 220-230-240V 50-60Hz (AC)                         [kA]   75% (50)    100%     100%       75%                      100%       100%      100%      100%       100%      100%      100%       100%      100%      100%
          Ics @ 415V 50-60Hz (AC)                                 [kA]    100%       100%     100%       75%                      100%       100%      100%      100%       100%      100%      100%       100%      100%      100%
          Ics @ 690V 50-60Hz (AC)                                 [kA]    75% (5)    100%     100%       75%                      100%       100%      100%      100% (3)   100%      100%      100%       100%      100%      100%


                                                                                                                                                      A (up to 630A), B (up to   A (up to 1000A) - B (800A)
          Utilization Category (IEC 60947-2)                                A              A              A                              A                                                             B                   B
                                                                                                                                                           500A)  (4)             (4)
          Icw                                                     [kA]      -              -              -                              -                    6                   10                  20                   20
          Reference Standard                                             60947-2       IEC 60947-2    IEC 60947-2                    IEC 60947-2          IEC 60947-2         IEC 60947-2          IEC 60947-2         IEC 60947-2
          Insulation behaviour                                                                                                                                                                                      
          Mounted on DIN rail                                            EN 50022     DIN EN 50022   DIN EN 50022                   DIN EN 50022              -                    -                   -                    -
                                                         [No. Operations]  25,000        25,000         25,000                         25,000               20,000              20,000               10,000              20,000
          Mechanical life
                                                     [No. Hourly operations]  240         240            240                            240                  120                 120                  60                   60
                                                                                                                                                       7.000 (400A) - 5.000
                                                         [No. Operations]  8,000         8,000          8,000                           8,000                                    5,000               3,000                3,000
          Electrical life @ 415 V (AC)                                                                                                                      (630A)
                                                     [No. Hourly operations]  120         120            120                            120                  60                   60                  60                   60
          Dimensions
          Fixed                                3 poles           [mm]  76.2 x 70 x 130  90 x 82.5 x 130  105 x 70 x 150             105 x 82.5 x 160    140 x 103 x 205     210 x 103.5 x 268     210 x 166 x 268     210 x 178 x 268
          (Width x Depth x Height)             4 poles           [mm]  101.6 x 70 x 130  120 x 82.5 x 130  140 x 70 x 150           140 x 82.5 x 160    186 x 103 x 205     280 x 103.5 x 268     280 x 166 x 268     280 x 178 x 268
          Trip units for power distribution
          TMD/TMA                                                                                                                                                            
          TMD/TMF
          Ekip Dip                                                                                                                                                                                                    
          Trip units for motor protection
          MF/MA                                                                                                                                           
          Ekip Dip                                                                                                                                                                                                    
          Ekip Touch                                                                                                                                                                                                   
          Interchangeable trip units                                                                                                                                                                                  
          Weight
          Fixed                                3/4 poles          [kg]   1.1 / 1.4                     1.7 / 2.1                       2.5 / 3.5          3.25 / 4.15           9.5 / 12            9.7 / 12.5           11 / 14
          Plug in (EF terminals)               3/4 poles          [kg]   2.21 / 2.82                   3.24 / 4.1                     4.19 / 5.52         5.15 / 6.65
          Withdrawable (EF terminals)          3/4 poles          [kg]                                                                 5 / 6.76            5.4 / 6.9           12.1 / 15.1         29.7 / 39.6           32 / 42.6

          (1) XT1 plug-in In max=125A
          Note: Higher kA (120, 150 & 200) available as indent.



     40   V16-PD-MCCB-R04                               www.ipd.com.au                             Phone: 1300 556 601