SACE TMAX XT MOULDED CASE CIRCUIT BREAKERS










 Size  XT1  XT2  XT3  XT4             XT5                 XT6 (2)              XT7                 XT7M
 Rated uninterrupted current  [A]  160  160  250  160 / 250  400 / 630  800 (6)  1000 / 1250 / 1600  800 / 1000 / 1250 / 1600
 Poles  [No.]  3, 4  3, 4  3, 4  3, 4  3, 4               3, 4                 3, 4                 3, 4
 (AC)                                                                                                              MCCB
 Rated service voltage, Ue  [V]  690  690  690  690  690  690                  690                 690
 50-60Hz
 Rated insulation voltage, Ui  [V]  800  1000  800  1000  1000  1000          1000                 1000
 Rated impulse withstand voltage, Uimp  [kV]  8  8  8  8  8  8                  8                   8
 Fixed, Withdrawable,   Fixed, Withdrawable,   Fixed, Withdrawable,
 Versions  Fixed, Plug-in (1)  Fixed, Plug-in        Fixed, Withdrawable  Fixed, Withdrawable  Fixed, Withdrawable
 Plug-in        Plug-in             Plug-in  (5)
 Breaking capacities according to IEC 60947-2  N  N  H  N  N  H  N  H  S  H  S       H         S         H
 Rated ultimate short-circuit breaking capacity, Icu
 Icu @ 220-230-240V 50-60Hz (AC)  [kA]  65  65  100  50  65  100  70  100  85  100  85  100    85        100
 Icu @ 415V 50-60Hz (AC)  [kA]  36  36  70  36  36  70  36  70  50  70    50         70        50        70
 Icu @ 690V 50-60Hz (AC)  [kA]  6  10  15  5  10  15  20  40  22  25      30         42        30        42
 Rated service short-circuit breaking capacity, Ics
 Ics @ 220-230-240V 50-60Hz (AC)  [kA]  75% (50)  100%  100%  75%  100%  100%  100%  100%  100%  100%  100%  100%  100%  100%
 Ics @ 415V 50-60Hz (AC)  [kA]  100%  100%  100%  75%  100%  100%  100%  100%  100%  100%  100%  100%  100%  100%
 Ics @ 690V 50-60Hz (AC)  [kA]  75% (5)  100%  100%  75%  100%  100%  100%  100% (3)  100%  100%  100%  100%  100%  100%


                               A (up to 630A), B (up to   A (up to 1000A) - B (800A)
 Utilization Category (IEC 60947-2)  A  A  A  A                                 B                   B
                                    500A)  (4)             (4)
 Icw  [kA]  -  -  -  -                 6                   10                  20                   20
 Reference Standard  60947-2  IEC 60947-2  IEC 60947-2  IEC 60947-2  IEC 60947-2  IEC 60947-2  IEC 60947-2  IEC 60947-2
 Insulation behaviour                                                                        
 Mounted on DIN rail  EN 50022  DIN EN 50022  DIN EN 50022  DIN EN 50022  -  -  -                    -
 [No. Operations]  25,000  25,000  25,000  25,000  20,000  20,000             10,000              20,000
 Mechanical life
 [No. Hourly operations]  240  240  240  240  120         120                  60                   60
                                7.000 (400A) - 5.000
 [No. Operations]  8,000  8,000  8,000  8,000             5,000               3,000                3,000
 Electrical life @ 415 V (AC)        (630A)
 [No. Hourly operations]  120  120  120  120  60           60                  60                   60
 Dimensions
 Fixed  3 poles  [mm]  76.2 x 70 x 130  90 x 82.5 x 130  105 x 70 x 150  105 x 82.5 x 160  140 x 103 x 205  210 x 103.5 x 268  210 x 166 x 268  210 x 178 x 268
 (Width x Depth x Height)  4 poles  [mm]  101.6 x 70 x 130  120 x 82.5 x 130  140 x 70 x 150  140 x 82.5 x 160  186 x 103 x 205  280 x 103.5 x 268  280 x 166 x 268  280 x 178 x 268
 Trip units for power distribution
 TMD/TMA                                              
 TMD/TMF
 Ekip Dip                                                                                      
 Trip units for motor protection
 MF/MA                             
 Ekip Dip                                                                                      
 Ekip Touch                                                                                     
 Interchangeable trip units                                                                    
 Weight
 Fixed  3/4 poles  [kg]  1.1 / 1.4  1.7 / 2.1  2.5 / 3.5  3.25 / 4.15  9.5 / 12  9.7 / 12.5       11 / 14
 Plug in (EF terminals)  3/4 poles  [kg]  2.21 / 2.82  3.24 / 4.1  4.19 / 5.52  5.15 / 6.65
 Withdrawable (EF terminals)  3/4 poles  [kg]  5 / 6.76  5.4 / 6.9  12.1 / 15.1  29.7 / 39.6      32 / 42.6

        (2) Not suitable for IT distribution Systems  (3) Ics = 75% In > 500A  (4) Category B: only when equipped with an electronic trip unit  (5) Plug-in/Withdrawable: max In 40°C=600A
        (6) 1000A only for fixed execution with EF, ES, R and FCCuAl terminals. EF terminals are supplied as standard if no other terminals are ordered