Page 683 - V16 Catalogue Final
P. 683
CAPACITOR PROTECTION
FUSE SELECTION FOR 3-PHASE CAPACITOR BANKS AT 415VAC
TECHNICAL
RESOURCES
Capacitor Bank Rating Recommended GEC,
ABB or IPD Fuse-Link Rating (A)
kVAr FLC (A) Type T ‘gG’ DIN Type ‘gL’ - ‘gG’
5 6.9 16 16
7.5 10.4 16 16
10 13.9 25 25
15 20.9 32 32
20 27.8 50 50
25 34.8 63 63
30 41.7 63 63
35 48.7 80 80
40 55.6 100 100
50 69.6 125 125
60 83.5 125 125
75 104 160 160
90 125 200 200
100 139 250 250
110 153 250 250
120 167 250 250
135 188 315 315
150 209 315 315
160 223 355 355
180 250 400 400
190 264 400 400
200 278 450 500
225 313 500 500
240 334 500 500
275 383 630 630
300 417 630 630
360 501 750 800
400 557 1000 1000
1. Recommended fuse ratings allow for a capacitor manufacturing tolerance of +10% on
the kVAr values and the possibility of up to 30% constant overload of a capacitor bank
due to harmonic currents.
2. Suitable adjustments to the recommended ratings may be necessary for high enclosure
(fluid environment) temperatures, refer to de-rating information indicated on page 677.
Phone: 1300 556 601 www.ipd.com.au V16-TR-R03 675