Page 133 - MCCB-XT2-XT4
P. 133

ABB | SACE Tmax XT

                          Interface the module has three signaling leds:








                                                               1                2




                                    Figure 33
                                     LEDs     Description
                                              Signals the on status and correct communication with Ekip Touch:
                                               • off: module off
                                               • on steady or flashing synchronized with the Power led of Ekip Touch: module on and
                                     Power
                                              communication with Trip unit present.
                                               • flashing not synchronized with the Power led of Ekip Touch (2 fast flashes per
                                              second): module on and communication with Trip unit absent
                                              Indicates the communication status on the bus:
                                               • off: device off line (with Status led off) , or in the error condition (with Status led
                                                                               (1)
                                     Network   on)
                                     Status (1)   • on steady: device on line, and assigned to a master (operating condition)
                                               • on flashing: device on line, but not assigned to a master (device ready to
                                              communicate)
                                              Indicates the communication status on the bus:
                                     Network    • Off: no error.
                                     Status (2)   • On fixed: device in bus off, or Network Power absent.
                                               • On flashing: I/O connection (cyclic data) in timeout

                                    (1)  the device has not yet sent the Duplicate ID sequence in line


                     Configurations Resistors can be connected to the CAN bus by configuring the dip-switches at the side of the module:



                                                     ON




                                                    1 234


                                    Figure 34

                                     Resistor   Dip        Description                                  Default
                                                           120 Ω termination resistor
                                     Rterm      1 and 2    Move dip-switches 1 and 2 to the ON position to   Off
                                                           connect Rterm

                                           IMPORTANT:

                                            •  move the dip-switches before connecting the module to Ekip Supply and the network
                                            •  the termination resistors must never be included in the nodes; inclusion of this capacitance
                                              could lead to a network with improper termination (impedance too high or too low), which
                                              could potentially cause a failure. For example, removal of a node comprising a termination
                                              resistor could lead to network failure
                                            •  the termination resistors must never be installed at the end of a drop line but only at the
                                              ends of the main trunk line










       131 | © 2022 ABB |  1SDH002031A1002 - ECN000212994             External electronic accessories | 6 - Ekip Com DeviceNet TM