Page 129 - MCCB-XT2-XT4
P. 129
ABB | SACE Tmax XT
5 - Ekip Com Profibus DP
Ekip Com Profibus DP is a communication accessory which allows Ekip Touch to be integrated into an RS-
485 network with Profibus communication protocol, with remote supervision and monitoring functions.
The module is configured as a Slave and remotely, you can:
• read Ekip Touch measurements and information
• manage certain controls, including opening and closing the actuator
• access information not available on the display
• If connected to a withdrawable version of the circuit-breaker, the allows the racked-in/racked-out
status to be detected
NOTE: the remote open and close commands of the circuit-breaker can only be executed if
Ekip Touch is in the Remote configuration
The System Interface document is available for mapping the module in its communication network. All the
required communication and command details are listed in the document (page 121).
Accessories Ekip Cartridge and Ekip Supply are required in order to connect Ekip Com Profibus DP to Ekip
Touch (page 122, 123).
Models Two different modules compatible with the Profibus protocol are available: Ekip Com Profibus DP and
Ekip Com Profibus DP Redundant.
The modules are identical in terms of characteristics and installation methods, except for: display menus,
cabling and addresses for system communication, which are specific for each module.
NOTE: if different indications are not given, the information in the next chapter is valid for
both models
The two modules can be connected at the same time to Ekip Touch so as to expand the potential of the
unit (e.g. for applications where high grid reliability is required).
IMPORTANT: each Ekip Touch can be fitted with only one module per type. The configuration
with two modules of the same model is not allowed (example: two Ekip Com Profibus
DP Redundant)
Connections For references about the connection and terminals, please consult document 1SdM000068r0001; use
Belden 3079A type cables or equivalent for the external cabling.
To connect the module to Ekip Supply and Ekip Cartridge, please consult document 1SdH002009A1503.
Power supply Ekip Com Profibus DP is supplied directly by the Ekip Supply module to which it is connected.
NOTE: communication between Ekip Touch and the module is interrupted in the absence
of auxiliary power supply
Interface the module has three signaling leds:
Figure 31
Continued on the next page
127 | © 2022 ABB | 1SDH002031A1002 - ECN000212994 External electronic accessories | 5 - Ekip Com Profibus DP