Page 128 - MCCB-XT2-XT4
P. 128

ABB | SACE Tmax XT

            Configurations via menu Local bus activation, which is essential for starting the communication between module and Ekip Touch,
                                    is available in the Settings menu (page 114).
                                    Two areas are activated if Ekip Touch detects the module correctly:
                                     •  information area in the About-Modules menu, containing the software version and serial number
                                       of the module
                                     •  specific configuration area in the Settings-Modules menu, where the following communication
                                       parameters can be configured
                                     Parameter    Description                                         Default
                                                  Module address; 1 to 247 range available
                                     Serial address   IMPORTANT: devices connected to the same network must  247 / 246  (1)
                                                     have different addresses
                                                  Data transmission speed; 3 options are available: 9600 bit/s,
                                     Baudrate                                                         19200 bit/s
                                                  19200 bit/s, 38400 bit/s
                                                  Defines the stop and parity bit; 4 options are available:
                                                   • 8,E,1 = 8 data bits, 1 EVEN parity bit, 1 STOP bit
                                     Physical
                                     protocol      • 8,O,1 = 8 data bits, 1 ODD parity bit, 1 STOP bit  8,E,1
                                                   • 8,N,2 = 8 data bits, no parity bit, 2 STOP bits
                                                   • 8,N,1 = 8 data bits, no parity bit, 1 STOP bit

                                    (1)  247 default of the Ekip Com Modbus RTU module; 246 default of the Ekip Com Modbus RTU
                                    Redundant module


              Remote configurations The operating configuration can be changed from slave to master via the service connector (via Ekip
                                    Connect) or via system bus communication so as to integrate the module into an interactive data
                                    exchange network (see description of Ekip Com Hub, page 151).
                                           IMPORTANT:

                                            •  In the Master configuration, the module does not allow data exchange as in the normal
                                              Slave function
                                            •  the presence of several masters in the same network can cause faulty operation


                Remote information Certain additional information concerning the version and status of the module is available via the service
                                    connector (via Ekip Connect) or by communication via system bus; the information includes: HW and Boot
                                    version, CRC status (correctness of the SW in the module).











































       126 | © 2022 ABB |  1SDH002031A1002 - ECN000212994              External electronic accessories | 4 - Ekip Com Modbus RTU