ABB | SACE Tmax XT

                          Interface the module has three signaling leds:














                                    Figure 41
                                     LEDs           Description
                                                    Signals the on status and correct communication with Ekip Touch:
                                                     • off: module off
                                                     • on steady or flashing synchronized with the Power led of Ekip Touch: module
                                     Power
                                                    on and communication with Trip unit present.
                                                     • flashing not synchronized with the Power led of Ekip Touch (2 fast flashes
                                                    per second): module on and communication with Trip unit absent
                                                    Indicate the status of the contacts of each output:
                                     I 11, I 12      • off: contact open
                                                     • on: contact closed
                                                    Indicate the status of the contacts of each input:
                                     O 11, O 12      • off: circuit open
                                                     • on: short circuit




                              Menu The specific configuration area will activate in the Settings - Modules menu if the Ekip Signalling 2K
                                    module is detected correctly by Ekip Touch.
                                    A specific menu containing the submenus of all the available and configurable inputs and outputs is
                                    available for each Ekip Signalling 2K module detected by Ekip Touch.


                   Input parameters All the available inputs enable the following parameters to be configured:
                                     Parameter      Description                                            Default
                                                    Defines whether the input is interpreted as ON by Ekip Touch when   Active
                                     Polarity
                                                    it is open (Active open) or when it is closed (Active Closed)  closed
                                                    Minimum activation time of the input before status change is
                                                    recognized; the delay is given in seconds and can be set within
                                                    range: 0 s to 100 s, in 0.01 s steps
                                     Delay              NOTES:                                             0.1 s
                                                         • if the input is deactivated before this time has elapsed the
                                                        status change is not recognized
                                                         • if delay = 0 s status change must still be more than 300 µS




























       157 | © 2022 ABB |  1SDH002031A1002 - ECN000212994                 External electronic accessories | 13 - Ekip Signalling 2K