Page 163 - MCCB-XT2-XT4
P. 163

Continued from the previous page                               ABB | SACE Tmax XT
                                     LEDs           Description
                                                    Signals the on status and correct communication with Ekip Touch:
                                                     • off: module off
                                                     • on steady or flashing synchronized with the Power led of Ekip Touch: module
                                     Power
                                                    on and communication with Trip unit present, flashing not synchronized with
                                                    the Power led of Ekip Touch (two fast flashes per second): module on and
                                                    communication with Trip unit absent
                                                    Indicate the status of the contacts of each output:
                                                     • off: contact open
                                                     • on: contact closed
                                     O SC
                                                         NOTE: The LED displays the state of the output: it can indicate
                                                        synchronization OK or KO, depending on the contact rest configuration
                                                        (normally open or closed)



            Configurations via menu The specific configuration area will activate in the Advanced - Synchrocheck menu if the Ekip Synchrocheck
                                    module is detected correctly by Ekip Touch.
                                     Parameter      Description                                            Default
                                                    Activates/deactivates the protection and its availability in the
                                     Enable                                                                Off
                                                    parameters menu
                                     Dead bar option  On = busbar activated; Off = dead busbar present     Off
                                                    Maximum external voltage (with dead busbar and configuration:
                                     Udead Threshold    Normal  is the first synchronism condition)
                                                           (2)
                                     (1)(2)         The value is given as both absolute value (V) and relative value (Un)   0.2 Un
                                                    and can be set within the range: 0.02 Un to 2 Un, in 0.001 Un steps
                                                    Minimum voltage for starting monitoring of external voltage (with
                                                    busbar activated) or internal voltage (with dead busbar and Normal
                                     Ulive Threshold  (2)(3)  configuration)                               0.5 Un
                                                    The value is given as both absolute value (V) and relative value (Un)
                                                    and can be set within the range: 0.5 Un to 1.1 Un, in 0.001 Un steps
                                                    Minimum time within which the Ulive Threshold condition must be
                                                    obtained in order to activate voltage monitoring
                                     Stability Time                                                        1 s
                                                    The value is given in seconds and can be set within the range: 100
                                                    ms to 30 s, in 1 ms steps
                                                    Maximum difference between internal and external voltage (first
                                                    synchronism condition)
                                     Delta Voltage                                                         0.12 Un
                                                    The value is given as both absolute value (V) and relative value (Un)
                                                    and can be set within the range: 0.02 Un to 0.12 Un, in 0.001 Un steps
                                                    Maximum difference between internal and external frequency
                                                    (second synchronism condition)
                                     Delta frequency  (4)                                                  0.1 Hz
                                                    The value is given in Hertz and can be set within the range: 0.1 Hz to
                                                    1 Hz in 0.1 Hz steps
                                                    Maximum difference between internal and external phase (third
                                                    synchronism condition)
                                     Delta phase  (4)                                                      50 °
                                                    The value is given in degrees and can be set within the range: 5° to
                                                    50° in 5° steps
                                                    With dead busbar and generator:
                                                     • Reversed = Ekip Synchrocheck/external contacts connected to the
                                     Dead bar
                                     configuration  generator                                              Standard
                                                     • Normal = Ekip Synchrocheck/external contacts connected to the
                                                    grid
                                                    Enables automatic synchronism control to be activated:
                                     Auto Live-dead    • Manual = Ekip Touch considers the Dead bar option parameter
                                     detect          • Automatic = Ekip Touch automatically assesses the configuration   Manual
                                                    to be actuated between the dead busbar and active busbar
                                                    Configuration for detecting dead busbar:
                                                     • Manual = Ekip Touch considers the Dead bar configuration
                                     Auto Deadbar
                                     detect         parameter                                              Manual
                                                     • Automatic = Ekip Touch automatically assesses the configuration
                                                    to be actuated between: Reversed and Normal
                                                    Rated voltage Un of installation; the value is given as absolute value
                                     Primary voltage                                                       100 V
                                                    (V) and can be set within the range: 100 V to 1150 V in variable steps.

                                                                                                Continued on the next page

       161 | © 2022 ABB |  1SDH002031A1002 - ECN000212994                 External electronic accessories | 14 - Ekip Synchrocheck