Page 162 - MCCB-XT2-XT4
P. 162
ABB | SACE Tmax XT
Power supply Ekip Com Synchrocheck is supplied directly by the Ekip Supply module to which it is connected.
NOTE: communication between Ekip Touch and the module is interrupted in the absence
of auxiliary power supply
Input Ekip Synchrocheck has an input (V S1 - V S2) for reading voltage, operation of which is ensured within the
ranges and with the performance given below:
Component Operating range Normal operating range Accuracy (1)
Voltage 0÷120 VAC 10 ÷ 120 VAC 1 % (2)
Frequency (3) 30÷80 Hz 30 ÷ 80 Hz 0,1 % (4)
Phase (5) - -180 ÷ +180 ° 1 °
(1) the accuracy values refer to normal operating ranges, as established by IEC 61557-12
(2) with busbar activated
(3) with the busbar activated, frequency measurement starts at ≥ 36 V AC and ends at ≤ 32 V AC
measured voltage
(4) in the absence of harmonic distortion
(5) phase measurement refers to the phase difference between internal and external voltage
Isolation transformer
An isolating transformer with the characteristics given below must always be installed between the
external contacts of the circuit-breaker and the input of the module:
Characteristics Description
• fixing: EN 50022 DIN 43880 rail
• material: self-extinguishing thermoplastic
Mechanical
• protection class: IP30
• electrostatic protection: with earth connector shield
• accuracy class: ≤ 0,2
• performance: ≥ 4 VA
• overload: 20% permanent
Electrical
• insulations: 4 kV between inputs and outputs, 4 kV between screen and
outputs, 4 kV between screen and inputs
• frequency: 45 to 66 Hz
Output Ekip Synchrocheck has an output (K S1 - K S2) used as synchronism contact.
The output is insulated from the unit and input, and has the following electrical characteristics:
Characteristics Maximum limit (1)
Maximum switchable voltage 150 VDC / 250 VAC.
2 A @ 30 VDC, 0,8 A @ 50 VDC, 0,2 A @ 150 VDC,
Breaking capacity
4 A @ 250 VAC
Dielectric strength between open contacts 1000 V AC (1 minute @ 50 Hz).
Dielectric strength between each contact and 1000 V AC (1 minute @ 50 Hz).
coil
(1) data relating to a resistive load
Interface the module has three signaling leds:
Figure 42
Continued on the next page
160 | © 2022 ABB | 1SDH002031A1002 - ECN000212994 External electronic accessories | 14 - Ekip Synchrocheck