Continued from the previous page                               ABB | SACE Tmax XT
                                     Parameter      Description                                            Default
                                                    Secondary voltage of the transformer; the value is given as absolute
                                     Secondary voltage value (V) and can be set within the range: 100 V to 120 V in variable   100 V
                                                    steps.
                                                    Line-to-line voltage entering the module among the 3 installation
                                     Concatenated Ref                                                      U12
                                                    voltages
                                                    Defines the rest status of the contact with synchronism not present
                                     Contact Type                                                          NO
                                                    between: open (NO) and closed (NC)

                                    (1)  parameter not available with busbar active and Auto deadbar detect= Manual
                                    (2)  with dead busbar and configuration: Reversed, the roles of the internal and external voltages are
                                    reversed
                                    (3)  10% hysteresis is applied to the  minimum voltage condition: once reached, the condition is lost if
                                    the voltage drops below 90% of the set limit
                                    (4)  parameter not available with dead busbar and Auto deadbar detect= Manual

                                           NOTE: all the thresholds have ±10% tolerance with the exception of:

                                            •  Voltage Delta; the tolerance is the higher value between: ±10% of the set threshold and 0.5%
                                              Un (with Un > 220 V) or 1% Un (with Un ≤ 220 V)
                                            •  Frequency Delta; the tolerance is the higher value between ±10% of the set threshold and
                                              0.02 Hz


              Remote configurations Additional parameters can be accessed via the service connector (via Ekip Connect) or via a system bus
                                    communication:

                                     Parameter  Description                                                Default
                                     Frequency   Activates (ON) or deactivates (OFF) frequency control for synchronism
                                     check      assessment                                                 ON
                                                Activates (ON) or deactivates (OFF) phase control for synchronism
                                     Phase check                                                           ON
                                                assessment
                                                Activates (YES) or deactivates (NO) circuit-breaker open status control for
                                     Evaluate CB   synchronism assessment
                                     status          NOTE: fourth synchronism condition with busbar active; second   NO
                                                    synchronism condition with dead busbar
                                                With active busbar, minimum time within which the Delta Phase condition
                                                must be obtained
                                                The value is given in seconds and can be set within the range: 100 ms to 3
                                                s, in 10 ms steps
                                     Minimum         NOTE: this is not a synchronism condition, but a parameter allowing
                                     matching       a discrimination to be made between correct and incorrect   100 ms
                                     time
                                                    combinations of the Delta Frequency and Delta Phase conditions.
                                                    Owing to worst case latencies, the time that effectively elapses
                                                    before synchronism is recognized may be longer than the set time
                                                (approx. 20 ms)