                 Output parameters All the available inputs enable the following parameters to be configured:
                                     Parameter          Description                                      Default
                                                        Event which activates the output and switches the contacts.
                                                        Different protection proposals, statuses and thresholds are
                                     Signal source      available on the display; the Custom mode can be configured  None
                                                        via Ekip Connect so as to extend the solutions and combine
                                                        several events
                                                        Minimum duration of the presence of the source before the
                                                        output is activated; the delay is given in seconds and can be
                                                        set within range: 0 s to 100 s, in 0.01 s steps
                                                            NOTES:
                                     Delay                                                               0 s
                                                             • the output will not be switched if the source is
                                                            deactivated before this time has elapsed
                                                             • if delay = 0 s the source must still be present for
                                                            longer than 300 µS
                                                        Defines the rest status of the contact with source not
                                     Contact Type                                                        NO
                                                        present between: open (NO) and closed (NC)
                                                        Allows the output (and relative status led) to be kept
                                     Latched            activated (On) or deactivated (Off) when the event   OFF
                                                        disappears
                                                        Defines the minimum closing time of the contact following
                                                        the rapid presence of sources:
                                                         • Source duration < min. activation = contact is activated for
                                     min Activation Time  the minimum activation time                    0 ms
                                                         • Source duration ≥ min. activation = contact is activated for
                                                        as long as the source persists
                                                        Choose between: 0 ms, 100 ms, 200 ms



                             About The specific menu of the module available in the About - Modules menu contains:
                                     •  the serial number and version of the module
                                     •  the statuses of the inputs (On/Off) and outputs (Open/Closed)


                               Test The test area in the Test menu is activated if the Ekip Signalling 2K module is detected correctly.
                                    For details of the test characteristics, please consult page 119.


                Remote information Certain additional information concerning the version and status of the module is available via the service
                                    connector (via Ekip Connect) or by communication via system bus; the information includes: HW and Boot
                                    version, CRC status (correctness of the SW in the module).