Page 191 - MCCB-XT2-XT4
P. 191

ABB | SACE Tmax XT

                      Power supply Ekip Com Hub is supplied directly by the Ekip Touch to which it is connected.
                                           NOTE: communication between Ekip Touch and the module is interrupted in the absence
                                           of auxiliary power supply


            Configurations via menu Local bus activation, which is essential for starting the communication between module and Ekip Touch,
                                    is available in the Settings menu (page 29).
                                    The following communication parameters can be configured if the module has been correctly detected by
                                    Ekip Touch in the Settings-Modules menu:
                                     Parameter    Description                                         Default
                                     Enable       Switches communication between module and server on/off.  Off
                                                  Defines whether the module has the dynamic (Off) or static (On)
                                     Static IP    IP address.                                         Off
                                     address ON
                                                  If = On all the associated parameters are enabled
                                     Static address
                                     IP address   Enables the static IP to be selected                0.0.0.0
                                     Static Network
                                     Mask         Enables the subnet mask to be selected              0.0.0.0
                                     Static Gateway  When there are several subnets, enables the IP address of the   0.0.0.0
                                     address      node to which the module is connected to be selected
                                     Enable SNTP   Allows the SNTP protocol for distribution of the clock and   Off
                                     client       synchronization signal to be enabled.
                                     SNTP Server   Allows the network server that supplies the SNTP to be set.  0.0.0.0
                                     Addr.
                                     Password     code required to register module on Cloud           ---

                                    The Remote FW update submenu enables the Firmware update function of the module to be managed;
                                    the following parameters are available:
                                     Parameter    Description                                         Default
                                                  Enables firmware update function of module to be remotely
                                     Enable                                                           OFF
                                                  activated/deactivated
                                                  The parameter is available when Enable = On and allows the
                                                  automatic update mode to be activated (On): in the presence
                                                  of new Firmware, this latter is updated automatically. If the
                                     Automatic    parameter is Off, updating must be performed in the Manual   OFF (manual)
                                                  mode: in the presence of new Firmware, the message Ekip
                                                  Com Hub FW Update appears in the status bar and updating is
                                                  performed via the Manual command
                                                  This parameter is available when Enable= On, with Automatic=
                                     Start FW     Off configuration and when new Firmware is present (see   Little endian
                                     update       description above); allows the Firmware update of the module to
                                                  run






























       189 | © 2022 ABB |  1SDH002031A1002 - ECN000212994                             Internal accessories | 7 - Ekip Com Hub
   186   187   188   189   190   191   192   193   194   195   196