Page 192 - MCCB-XT2-XT4
P. 192
ABB | SACE Tmax XT
Information in menu The following information will be available in the About-Modules menu if Ekip Touch has detected the
module correctly:
Information Description
SN and version Identifier and SW version of the module
Address of the module, assigned to the module by a DHCP server at the time
of connection to the network in the case of configuration with a dynamic IP, or
IP address can be set via the menu in the event of a static IP
NOTE:without a DHCP server, the module automatically adopts a random
IP address within the 169.254.xxx.xxx range
Subnet mask; identifies the method for recognizing the subnet to which the
Network Mask modules belong and enables modules to be searched for within a defined set
of recipients.
IP address of the node to which the module is connected, in the presence of
Gateway address
several subnets
Address assigned by ABB, with OUI (Organizationally Unique Identifier) equal
MAC address
to ac:d3:64, which uniquely identifies the manufacturer of an Ethernet device
Remote configurations Additional parameters can be accessed via the service connector (via Ekip Connect) or via a system bus
communication:
Information Description Default
Allows the CRL (Certificate Revocation List) to be used to
CRL Enable
ascertain whether the server certificate is valid
Clock update
hardening Enables control of the time reference transmitted by the SNTP
enable server
SNTP Server Enables the position of the SNTP server to be set in relation to
Location the network in which the module is installed
SNTP Time
zone Defines the time zone to be used for synchronism +00:00
SNTP Daylight Used to select whether daylight saving time is present (ON) or
Saving Time not (OFF) in the country to which the synchronization time refers OFF
Permits (Enabled ARP) the periodic generation of a Gratuitous
Disable ARP message, used by Ekip Connect to rapidly find the modules ARP Enabled
Gratuitous ARP
via Ethernet scan without knowing the IP address beforehand
Cloud data Enables/disables the function that collects and transmits the
send enable module data OFF
JSON data Allows the compressed format of the JSON file sent to Cloud to Disabled
compression be selected (enable)
190 | © 2022 ABB | 1SDH002031A1002 - ECN000212994 Internal accessories | 7 - Ekip Com Hub